Super Systems 7EK 31082 User Manual

Page 7

Advertising
background image

2

GB

LINEAR INPUT

Fig. 4 mA, mV AND V INPUTS WIRING

NOTE:
1) Don’t run input wires together with power cables.
2) Pay attention to the line resistance; a high line

resistance may cause measurement errors.

3) When shielded cable is used, it should be grounded at

one side only to avoid ground loop currents.

4

RTD

1

3

4

RTD

1

3

Shield

_

+

mA,

mV

or

V

3

+

_

G

mA
mV

or

V

1

3

1

RTD INPUT

Fig. 3 RTD INPUT WIRING

Input circuit: current injection (135

mA).

Line resistance: automatic compensation up to 20

W/wire

with no measurable error.
Calibration: according to DIN 43760

NOTE:
1) Don’t run input wires together with power cables.
2) Pay attention to the line resistance; a high line

resistance may cause measurement errors.

3) When shielded cable is used, it should be grounded at

one side only to avoid ground loop currents.

4) The resistance of the 3 wires must be the same.

Input type

13
14
15
16
17
18
19
20

0 - 60 mV

12 - 60 mV

0 - 20 mA
4 - 20 mA

0 - 5 V
1 - 5 V
0 - 10 V
2 - 10 V

impedance

> 1 M

W

< 5

W

> 200 k

W

> 400 k

W

Accuracy

0.2 % + 1 digit

@ 25°C

XKSser1-A0.p65

10/19/01, 1:37 PM

2

Advertising