Super Systems 7EK 31082 User Manual

Page 8

Advertising
background image

3

GB

B) LOGIC INPUT
Safety note:
1) Do not run logic input wiring together with power

cables.

2) Use an external dry contact capable of switching 0.5

mA, 5 V DC.

3) The instrument needs 100 ms to recognize a contact

status variation.

4) The logic inputs are NOT isolated by the measuring

input. A duble or reinforced isolation between logic
inputs and power supply must be assured by the
external elements.

Fig. 5 - LOGIC INPUT WIRING

This instrument is provided with 3 logic inputs.
The binary combination of the logic input 1 and 3 allows to
select the operative set point according with the following
table:

logic input 3

logic input 1

op. set point

open

open

SP

open

close

SP2

close

open

SP3

close

close

SP4

The logic input 2 function is programmed by P 24
parameter.

C) VALVE MOTOR DRIVE OUTPUT.

Fig. 6 - SERVOMOTOR WIRING

The two relay outputs are interlocked.
Potentiometer type: from 100

W to 10 kW.

Minimum working stroke: 50 % of the potentiometer
rang in order tu assure the 1% display resolution.

NOTES:
1) Before connecting the instrument to the power line, make

sure that line voltage and the load current are in accord-
ance with the contact rating (3A/250V AC on resistive
load).

2) To avoid electric shock, connect power line at the end of

the wiring procedure.

3) For servomotor connections use No 16 AWG or larger

wires rated for at last 75 °C.

4) Use copper conductors only.
5) Don’t run input wires together with power cables.
6) For feedback potentiometer, use shielded cable with the

shield connected to the earth at one point only.

7) The relay outputs are protected by varistor against

inductive load with inductive component up to 0.5 A.

8

Log. input 3

7

Log. input 2

6

5

Log. input 1

17

18

19

Servo-

motor

Power

line

20

21

22

s (Open the valve)

t (Close the valve)

Feedback

potentiometer

Shield

XKSser1-A0.p65

10/19/01, 1:37 PM

3

Advertising