12

GB

rEV = reverse action (relay de-energized in alarm condi-

tion)

P29 = Alarm 2 stand-by function (mask alarm)
Available only when P9 is different from "nonE".

OFF = Stand by (mask) disabled
On = Stand by (mask) enabled

P30 = Alarm 3 stand-by function (mask alarm)
Available only when P11 is different from "nonE".

OFF = Stand by (mask) disabled
On = Stand by (mask) enabled

P31 = OFFSET applied to the measured value
This will set a constant OFFSET throughout the readout
range. It is skipped for linear inputs
-

For readout ranges with decimal figure, P31 is
programmable from -19.9 to 19.9.

-

For readout ranges without decimal figure, P31 is
programmable from -199 to 199.

P32 = Displayable protected parameters
This parameter is skipped when P18 = 0.

OFF = Protected parameters cannot be displayed.
On =

Protected parameter can be displayed.

P33 = SMART function
0 = SMART function disabled.
1 = SMART function in NOT protected by safety lock.
2 = SMART function is under safety lock protection.

Real curve

Readout

Adjusted
curve

Input

P31

Closed = MANUAL

rE.dr =

Logic input 2 used for REVERSE/ DIRECT
control mode selection.
Open = REVERSE
Closed = DIRECT
NOTE: this selection is available only when P5
= "Sñ.OL" or "Sñ.CL".

P25 = Cooling media.
Available only when the device is configured with two
control outputs.
AIr = Air

OIL = Oil

H2O = water

Changing P25 parameter, the instrument forces the cycle
time and relative cooling gain parameter to the default
value related with the chosen cooling media.
When P25 = AIr

- Cyx = 10 s and rC = 1.00

P25 = OIL

- Cyx = 4 s and rC = 0.80

P25 = H2O

- Cyx = 2 and rC = 0.40

P26 = Alarm 1 action
Available only when P7 is equal to "AL1.P" or "AL1.b" or
"AL1.d".
dir

= direct action (relay energized in alarm condition)

rEV = reverse action (relay de-energized in alarm

condition)

P27 = Alarm 1 stand-by function (mask)
Available only when P7 is equal to "AL1.P" or "AL1.b" or
AL1.d".
OFF = stand-by function (mask alarm) disabled
On = stand-by function (mask alarm) enabled
NOTE: If the alarm is programmed as band or deviation
alarm, this function masks the alarm condition after a set
point change or at the instrument start-up until the
process variable reaches the alarm threshold plus or
minus hysteresis. If the alarm is programmed as a
process alarm, this function masks the alarm condition at
instrument start-up until the process variable reaches the
alarm threshold plus or minus hysteresis.

P28 = Action of the out 4
Available only when P9 or P11 are different from "nonE" or
P51 is different from "diS".
dir

= direct action (relay energized in alarm condition)