Testing the control network

4. Press

Enter

.

The ping command should return the IP address of the device, as in the following
example:

Pinging root_gige_1.mycorp.com [192.168.100.61] with
32 bytes of data:

Reply from 192.168.100.61: bytes=32 time=10ms TTL=127

Reply from 192.168.100.61: bytes=32 time<10ms TTL=127

Reply from 192.168.100.61: bytes=32 time<10ms TTL=127

Reply from 192.168.100.61: bytes=32 time<10ms TTL=127

This verifies that the name of the device is being correctly resolved to the IP
address, which indicates that on the Control Point PC the host table entry is correct.

5. Ping the other K2 Storage System devices to which you have assigned control

network IP addresses.

6. Go to each Windows device in the K2 Storage System and repeat this procedure.

This verifies that network communication is correct to and from all devices.