130

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

5 Troubleshooting

5

Troubleshooting

Fault Detection

Fault Displays, Causes, and Possible Solutions

Faults are detected for drive protection, and cause the drive to stop while triggering the fault output terminal MA-MB-
MC. Remove the cause of the fault and manually clear the fault before attempting to run the drive again.

Table 35 Detailed Fault Displays, Causes, and Possible Solutions

Digital Operator Display

Fault Name

boL

Braking Transistor Overload
The braking transistor has reached its overload level.

bUS

Option Communication Error

• The connection was lost after establishing initial communication.
• Only detected when the Up/Down command speed reference is assigned to an option card.

CE

MEMOBUS/Modbus Communication Error
Communication data was not received for the amount of time set in parameter, H5-09
Communication Fault Detection Time.

CF

Control Fault
The torque limit was reached continuously for three seconds or longer while ramping to stop in OLV
Control.

CoF

Current Offset Fault
The current sensor is damaged or there was residual induction current in the motor (e.g., during
sudden deceleration or when coasting) when the drive attempted to start the motor.

or

<1>

CPF00 or CPF01

Control Circuit Error

CPF02

A/D Conversion Error
An A/D conversion error or control circuit error occurred.

CPF03

Control Board Connection Error
Connection error between the control board and the drive

CPF06

EEPROM Memory Data Error
An error in the data saved to EEPROM

CPF07

Terminal Board Connection Error

CPF08

to

,

to

<1>

CPF11 to CPF14,

CPF16 to CPF21

Control Circuit Error

CPF22

Hybrid IC Failure

CPF23

Control Board Connection Error
Connection error between the control board and the drive

CPF24

Drive Unit Signal Fault
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered
up).

CPF25

Terminal Board not Connected

to

CPF26 to CPF34

Control Circuit Error
CPU error

CPF35

A/D Conversion Error
An A/D conversion error or control circuit error occurred.