5 Troubleshooting

136

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

ov

DC Bus Overvoltage
The DC bus voltage exceeded the trip point.
For 200 V class: approximately 410 V
For 400 V class: approximately 820 V
For 600 V class drives: approximately 1040 V

PASS

MEMOBUS/Modbus Communication Test Mode Complete

PGo

Encoder Disconnected (for Control Mode with Encoder)
Detected when no encoder signal is received for a time longer than setting in F1-14.

PGoH

Encoder Disconnected (detected when using an encoder)
Encoder cable has become disconnected.

SE

MEMOBUS/Modbus Self Test Failed

TrPC

IGBT Maintenance Time (90%)
IGBTs have reached 90% of their expected performance life.
Note: This alarm will not trigger a multi-function output terminal that is set for alarm output (H2-

=

10).

UL3

Undertorque Detection 1
Drive output current (or torque in OLV, CLV, CLV/PM) less than L6-02 for longer than L6-03 time.

UL4

Undertorque Detection 2
Drive output current (or torque in OLV, CLV, CLV/PM) less than L6-05 for longer than L6-06 time.

Uv

Undervoltage
One of the following conditions was true when the drive was stopped and a Up/Down command was
entered:

• DC bus voltage dropped below the level specified in L2-05.
• Contactor to suppress inrush current in the drive was opened.
• Low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC bus

voltage is under L2-05.

voF

Output Voltage Detection Error
There is a problem with the output voltage.

<1> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-1, ISO/EN

13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.

Digital Operator Display

Minor Fault Name