B Parameter Table

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

193

Par

ame

te

r Ta

ble

B

L8-12

Ambient Temperature
Setting

Enter the ambient temperature. This value adjusts the oL2 detection level.

Default: 40

°C

Min: -10

°C

Max: 50

°C

L8-15

oL2 (drive overload)
Characteristics Selection at
Low Speeds

0: No oL2 level reduction below 6 Hz.
1: oL2 level is reduced linearly below 6 Hz. It is halved at 0 Hz.

Default: 1
Min: 0
Max: 1

L8-27

Overcurrent Detection
Gain

Sets the gain for overcurrent detection as a percentage of the motor rated current.
Overcurrent is detected using the drive’s overcurrent level or the value set to L8-27,
whichever is lower.

Default: 300.0%
Min: 0.0%
Max: 300.0%

L8-29

Current Unbalance
Detection (LF2)

0: Disabled
1: Enabled

Default: 1
Min: 0
Max: 1

L8-35

<1>

Installation Selection

0: IP00 enclosure drive
2: IP00 enclosure drive with top protective cover

Default:

<4>

Min: 0
Max: 2

L8-38

Automatic Torque Boost
Selection

Torque Boost increases the output current limit while decreasing the carrier frequency
when the output current exceeds a certain value.
0: Disabled
3: Enabled

Default: 0
Min: 0
Max: 3

L8-39

Reduced Carrier
Frequency

Sets the reduced carrier frequency used by the Torque Boost function.

Default: 3.0 kHz
Min: 1.0 kHz
Max: 15.0 kHz

L8-55

Internal Braking Transistor
Protection

0: Disabled. L8-55 should be disabled when using a regen converter or an optional
braking unit.
1: Protection enabled.

Default: 1
Min: 0
Max: 1

L8-62

Operation Selection at
Input Phase Loss

Sets stopping method when a Input phase loss fault (PF) occurs. See parameter L8-05.
0: Ramp to Stop - Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to Stop
2: Fast Stop - Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only - Drive continues operation.

Default: 1
Min: 0
Max: 3

L8-77

Oscillation Suppression

Used to suppress speed oscillations that occur with an unloaded motor and that have
the same frequency as the output frequency.

Default: 0
Min: -100
Max: 100

L8-88

Safe Disable Operation
Mode

0: Mode 0
1: Mode 1

Default: 1
Min: 0
Max: 1

L8-89

<44>

Current Monitoring
Selection

Enables or disables the Current Monitoring function.
0: Disabled
1: Enabled

Default: 0
Min: 0
Max: 1

L8-99

<44>

Current Monitoring Level

Sets the current monitoring level as a percentage of the drive’s rated current. Sets the
level of current used for L8-89 and H2-

= 5C.

Default: 10.0%
Min: 0.0%
Max: 50.0%

<1> Parameter setting value is not reset to the default value when the drive is initialized.

<4> Default setting is determined by the drive model (o2-04).

<44> Available in drive software versions PRG: 7017 or later.

No.

Name

Description

Setting