4 Start-Up Programming & Operation

70

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

Flowchart D: PG Encoder Offset Auto-Tuning

The flowchart below covers Rotational and Stationary Auto-Tuning procedures used to automatically set up the PG
encoder offset. PG encoder Offset Tuning should be performed when the PG encoder offset (T2-17) is unknown, when a
PG encoder offset value has been set but problems with the speed feedback occur, or when the PG encoder is replaced.

Figure 39 PG Encoder Offset Auto-Tuning

<1> If an LED operator is used, the display shows “

”.

<2> If an LED operator is used, the display shows “

”.

Press the Up key until “Tuning Ready” is displayed.

Press the Up key until “Tuning Ready” is

displayed.

START

Has all motor and PG

encoder data been

set correctly?

FINISH

No

Yes

Press the Run key on the digital operator and wait until

Auto-Tuning is finished.

Tuning

Successful?

No

Select Initial Magnet Pole Search Parameter Auto-Tuning T2-01 = 3.

Set the motor and PG encoder data manually or

perform motor data Auto-tuning.

Yes

(Stationary PG Encoder Offset

Auto-Tuning possible)

Select Stationary Encoder Offset Auto-Tuning

T2-01 = 4.

Press the Run key on the digital operator

and wait until Auto-Tuning is finished.

Set terminals H1-HC and H2-HC if Safe Disable function is used.

Set the Baseblock input (H1-

= 8/9) if used.

Close the motor contactor(s).

Press the Up key until “Tuning Ready” is

displayed.

Select Rotational PG Encoder Offset

Auto-Tuning T2-01 = 10.

Press the Run key on the digital operator

and wait until Auto-Tuning is finished.

Uncouple motor and the mechanical system

of the elevator (remove ropes).

Tuning

Successful?

Yes

Open terminals H1-HC and H2-HC if used during the normal sequence.

Open the motor contactor(s).

Open the Baseblock input (H1-

= 8/9) if used.

No - “Er-22”

Rotational PG Encoder Offset Auto-Tuning necessary

Apply the brake.

Release the brake.

Recouple the motor (ropes) to the load if decoupled for tuning.

Refer to

Remove the Fault/Alarm source

and repeat Auto Tuning.

Tuning

Successful?

Refer to

Remove the Fault/Alarm source

and repeat Auto Tuning.

No

Yes

Absolute PG

encoder used?

Absolute PG encoder

necessary for driving the motor.

Change the PG option card and

use an absolute PG Encoder

(EnDat, ...).

No

(PG-X3, Incremental
PG encoder used)

Yes
(EnDat, ...)

<1>

<2>

<1>

<1>

Auto-Tuning Fault Detection

on page 138

.

Auto-Tuning Fault Detection

on page 138

.

YEA_comm
on