7 Option Card Installation

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

151

Op

tion

Ca

rd

In

st

al

lat

io

n

7

5.

For the PG-B3 and PG-X3 Option, wire the motor PG encoder to the terminal block. Refer to

Figure 91

and

Figure 95

for wiring instructions.

Refer to Terminal Functions on page 152

for a detailed description of the option terminal functions.

Connecting PG-B3 Option

Parameter Settings and Connections for Different Encoder Types

• Connecting a Single-Pulse Encoder

When using a single-pulse encoder in V/f with PG control mode, connect the pulse output from the PG to the option and
set drive parameter F1-21 to 0.

• Connecting a Two-Pulse Encoder

When using a two-pulse encoder, connect the A and B pulse outputs on the PG to the option and set F1-21 to 1.
When using a two-pulse encoder in Closed Loop Vector control mode, connect pulse outputs A and B from the encoder
to the corresponding terminals on the option.

• Connecting a Two-Pulse Encoder with Z Marker Pulse

When using a two-pulse encoder with Z marker pulse, connect the A, B, and Z pulse outputs to the corresponding
terminals on the option.

Connection Diagram of PG-B3

Refer to

Table 46

for a detailed description of the option board terminal functions.

Refer to

Wire Gauges and Tightening Torques on page 153

for information on making cables.

Figure 91 PG-B3 Option and Encoder Connection Diagram

Note: The PG-B3 Option reads a maximum input frequency from the PG encoder of 50 kHz. Be sure to select an PG encoder with an

output pulse frequency of maximum 50 kHz when operating at maximum speed.

Control Method

V/f with PG

Closed Loop Vector

No. of Encoders

1 (CN5-C)

2 (CN5-B)

1 (CN5-C)

2 (CN5-B)

Single Pulse (A)

F1-21 = 0

F1-37 = 0

N/A

N/A

Two Pulse (AB Quadrature)

F1-21 = 1

F1-37 = 1

No setting required

No setting required

Two Pulse with Marker (ABZ)

F1-21 = 1

F1-37 = 1

No setting required

No setting required

<1> Ground the shield on the PG side and the drive side. If noise problems arise in the PG signal, remove the shield ground from one end of the

signal line or remove the shield ground connection on both ends.

Twisted-pair shielded line

Main circuit terminal

Control circuit terminal

M

A+
A



B



Z



B+

Z+

AO
IG
BO
IG
ZO
IG

FE

IP
IG

TB1

SD

TB2

NC

CN5

PG

B3

Option

U/T1
V/T2

W/T3

R/L1
S/L2
T/L3

FE

YASKAWA

Drive

Ground wire

A pulse monitor signal

B pulse monitor signal

Z pulse monitor signal

PG

3
4
5
6

E

1
2

B3

TOEP_C710616_38F_5_0.book 151 ページ 2013年12月4日 水曜日 午前9時56分