6 Periodic Inspection & Maintenance

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

147

Pe

ri

odic

Inspe

c

ti

on &

Maint

ena

nc

e

6

3.

Slide the terminal board as illustrated by the arrows to remove it from the drive along with the bottom cover.

Figure 75

Figure 82 Drive Replacement: Remove the Control Terminal Board

Figure 76

Figure 83 Drive Replacement: Removable Control Terminal Board

Disconnected from the Drive

4.

Disconnect all option cards and options. Make sure they are intact before reusing them.

5.

Replace the drive and wire the main circuit.

Installing the Drive

1.

After wiring the main circuit, connect the terminal block to the drive as shown in

Figure 84

. Use the installation

screw to fasten the terminal block into place.

Figure 77

Figure 84 Drive Replacement: Installing the Control Terminal Board

2.

Reconnect all options to the new drive in the same way they were installed in the old drive. Connect option
boards to the same option ports in the new drive that were used in the old drive.

3.

Put the terminal cover back into its original place.

4.

After powering on the drive, all parameter settings are transferred from the terminal board to the drive memory. If
an oPE04 error occurs, load the parameter settings saved on the terminal board to the new drive by setting
parameter A1-03 to 5550. Reset the Maintenance Monitor function timers by setting parameters o4-01 through
o4-12 to 0, and parameter o4-13 to 1.