S3-14: Torque Compensation Diminish Speed

Sets the speed level for torque compensation to diminish during the time determined by S3-15. Set as a percentage of the
maximum output frequency (E1-04). A setting of 0.0% disables this function.

S3-15: Torque Compensation Diminish Time

Sets the time for torque compensation to diminish when motor speed reaches the level set in S3-14.

S3-16: Torque Limit Reduction Time

After Position Lock at stop, S3-16 determines the length of time to reduce the torque limit rate =

S3-20: Dwell 2 Speed Reference

Sets the speed reference for the Dwell 2 function.

Note: Setting this parameter to 0.00 disables the Dwell 2 function.

Figure 44

Figure 49 Dwell Speed Reference at Start

S3-21: Dwell 2 End Speed

The Dwell 2 function will end when the drive reaches this speed. A setting of 0.00 will disable the acceleration rate switch
that occurs at the end of Dwell 2.

No.

Parameter Name

Setting Range

Default

S3-14

Torque Compensation Diminish Speed

0.0 to 200.0%

0.0%

No.

Parameter Name

Setting Range

Default

S3-15

Torque Compensation Diminish Time

0 to 5000 ms

1000 ms

No.

Parameter Name

Setting Range

Default

S3-16

Torque Limit Reduction Time

0 to 10000 ms

100 ms

No.

Parameter Name

Setting Range

Default

S3-20

Dwell 2 Speed Reference

0.00 to 100.00%

0.00%

No.

Parameter Name

Setting Range

Default

S3-21

Dwell 2 End Speed

0.00 to 100.00%

0.00%

Torque 300%

S3-16

Run Command

C1-07

C2-01

S3-21

C1-01

ON

SFS output

Motor speed

S3-20