Yaskawa CIMR-LU Drives User Manual

Page 41

Advertising
background image

3 Electrical Installation

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

41

El

ec

tr

ical

I

n

st

al

lat

io

n

3

Note: When connecting peripheral devices and options to the terminals –, +1, +3, B1, and B2, refer to the instruction manuals for each

device. For more information, contact Yaskawa or your nearest sales representative.

4A0260

R/L1, S/L2, T/L3

3/0

× 2P

2/0 to 600

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

3/0

× 2P

2/0 to 600

–, +1

3/0 to 600

+3

1 to 325

M10

18 to 23

(159 to 204)

2

2 to 350

M12

32 to 40

(283 to 354)

4A0304

R/L1, S/L2, T/L3

4/0

× 2P

3/0 to 600

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

4/0

× 2P

3/0 to 600

–, +1

4/0 to 600

+3

3/0 to 600

M10

18 to 23

(159 to 204)

1

1 to 350

M12

32 to 40

(283 to 354)

4A0370

R/L1, S/L2, T/L3

300

× 2P

4/0 to 300

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

300

× 2P

4/0 to 300

–, +1

3/0 to 300

+3

3/0 to 300

1

1 to 3/0

4A0450

R/L1, S/L2, T/L3

3/0

× 4P

3/0 to 300

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

3/0

× 4P

3/0 to 300

–, +1

1/0 to 300

+3

1/0 to 300

1/0

1/0 to 300

4A0605

R/L1, S/L2, T/L3

300

× 4P

4/0 to 300

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

300

× 4P

4/0 to 300

–, +1

1/0 to 300

+3

1/0 to 300

2/0

2/0 to 300

<1> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an ELCB.

<2> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an ELCB, or use copper wire of 10 mm

2

(AWG 8).

Model

CIMR-LU

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N m (lb.in.)

TOEP_C710616_38F_5_0.book 41 ページ 2013年12月4日 水曜日 午前9時56分