11 setting i/o data, Channel number, Input data – Yaskawa MP940 User Manual

Page 135

Advertising
background image

MP940 Functions

4.4.11 Setting I/O Data

4-42

4.4.11 Setting I/O Data

Click the

I/O Data Settings

Tab.

Channel Number

The channel number is always displayed as CH#1.

Input Data

• Operating Status (IW0002)

The status of each bit in the operation status register is displayed as either ON

or

OFF

. The leading input register is the status word.

Bit No.

Status Name

Meaning

0

Data Setting Error

ON: Data setting error has occurred.

1

Fix Parameter Setting Error

ON: Fixed parameter setting error has occurred.

2

Count Value Preset

ON: Count has been preset.

3

PI Latch Detected

ON: PI latch has been completed.

4

A/B Pulse 0

ON: Feedback pulse is ±1 max.

5

Coincident Detection Signal

ON: Coincidence detection signal is ON (Unit:
pulse)

6 to 8

Not used

---

9

Writing Fix Parameter Now

ON: Writing online parameters

10

A-pulse Disconnect Indication ON: Pulse disconnected

11

B-pulse Disconnect Indication ON: Pulse disconnected

12 to 14

Not used

15

Module Ready

ON: Counter Module ready

Advertising