7.5 System Register Configuration and Error Status

Extended System Service Execution Status

7-70

Extended System Service Execution Status

The data in these registers give the execution status of the system when the Units are extended.

Alarm History Information

This section gives the register configuration of and details on the alarm history information in the system
registers.

Register Configuration

Name

Register Address

Remarks

Data Trace Definition Exis-
tence

SW15998

SB159980

Group 1

0: Definition does not

exist

1: Definition exists

SB159981

Group 2

SB159982

Group 3

SB159983

Group 4

SB159984 to
SB15998F

Reserved for system.

Data Trace Execution Status

SW15999

SB159990

Group 1

0: Tracing in progress
1: Tracing stopped

SB159991

Group 2

SB159992

Group 3

SB159993

Group 4

SB159994 to
SB15999F

Reserved for system.

Group 1 Record No.

SL16000

Latest record number in group 1.

Group 2 Record No.

SL16002

Latest record number in group 2.

Group 3 Record No.

SL16004

Latest record number in group 3.

Group 4 Record No.

SL16006

Latest record number in group 4.

Reserved for system.

SL16008

Reserved for system.

Reserved for system.

SL16010

Reserved for system.

Name

Register Addresses

Remarks

Current Alarm

SW16200

Cleared when the power is turned ON.

Alarm History Entries

SW16201

Number of alarm history entries

Alarm Clear

SW16202

1: Alarm cleared
2: Current alarm and history cleared

Alarm History

SW16203 to SW16218

Alarm History Entry 1

Refer to the following sections for
details.

Details (page 7-71)

SW16219 to SW16231

Alarm History Entry 2

SW17787 to SW17802

Alarm History Entry
100

Reserved for system.

SW17803 to SW17999

··