Emerson 250-400kVA User Manual

Page 50

Advertising
background image

UPS Alarm and Status Messages

44

Batt Discharging

The UPS is on battery.

The most common reason for going to battery is a

loss of rectifier input power (power outage).

This alarm is self-clearing. When the condition is

no longer present, the alarm and any control

activity tied to the alarm reverts to normal.

Press “SILENCE” to silence the audible alarm.

Observe the One-Line Display. If the input line is

orange, black, or gray, the battery discharging

condition is normal.

If the input line on the One-Line Display is green,

check the Active Event Window for potential fault

conditions that could explain why the UPS is on

battery. An example of this could be “Rectifier

Fault.”

Monitor the UPS during the battery discharge. The

display shows the discharge curve of the battery.

When the Battery Voltage Line touches the End of

Discharge Line, the UPS shuts down.

Check the bypass line on the One-Line Display. If

the line feeding the Static Bypass Switch (BPSS) is

green, the unit can be transferred to bypass by

pressing “Transfer,” “Bypass” to transfer the load to

the bypass source. Note that transferring to bypass

could expose the load to an outage if the bypass

source fails.

If the battery is discharging because of a fault such

as “Rectifier Fault” in the Active Event Window

rather than an actual power outage, transfer to

bypass if available, and contact your factory-

authorized service provider.

Batt Equalizing

The batteries are being equalized.

Battery equalization stops automatically based on

the Equalize Time Setting.

This status message is self-clearing. When the

condition is no longer present, the message and

any control activity tied to the status event reverts

to normal.

In normal operation, no user response is required.

Equalize charge can be terminated at any time by

pressing “Battery Management,” “Manual Battery

Equalize,” “Stop.”

Batt Ground Fault

Detected battery ground current exceeds the trip

setting.

A possible symptom that could cause this alarm is

a leaking battery.

This alarm has a higher detection setpoint than

“Battery Ground Fault Current Warning,” and if

present, means that the Battery Ground Fault

Current is excessive.

This alarm could cause Battery Breakers to trip if

the “Battery Ground Fault Trip Enable” setting is

enabled.

Press “SILENCE” to silence the audible alarm.

Are any Battery Circuit Breakers tripped?

Perform a visual inspection of the batteries in the

tripped string(s). Look for signs of leaking battery

acid or excessively corroded battery terminals.

If there are no visible signs of defective batteries,

press “RESET” to try and clear the alarm.

Close any open breakers one at a time, pressing

“RESET” after each one to see which string is

causing the alarm. The string reporting the fault,

when online, will not allow the alarm to reset.

Once the location is identified, or if the battery string

tests are inconclusive, contact your factory-

authorized service provider.

Table 7

Liebert NXL alarm and status messages (continued)

Event Message

Event Definition

Recommended Action

Advertising