Emerson 250-400kVA User Manual

Page 53

Advertising
background image

UPS Alarm and Status Messages

47

Breaker Close Fail

This is a summary event that informs the user that

a circuit breaker that was either signaled to close

or was manually closed failed to report a closed

status.

The Breaker Close Fail event indicates a

mismatch between the expected state of a

breaker and the reported state of the breaker.

Press “SILENCE” to silence the audible alarm.

Check the One-Line Display and the Active Event

Window to determine which breaker or switch is

open.

If the open breaker cannot be reset or closed, or if

all breakers are closed but the One-Line Display

does not agree, or the alarm cannot be cleared,

contact your factory-authorized service provider.

Breaker Open Fail

This is a summary event that informs the user a

circuit breaker that was either signaled to open or

was manually opened failed to report an open

status.

The Breaker Open Fail event indicates a

mismatch between the expected state of a

breaker and the reported state of the breaker.

Press “SILENCE” to silence the audible alarm.

Check the One-Line Display and the Active Event

Window to determine which breaker or switch that

should be open is still closed.

If a breaker that should be open shows closed, or if

the breaker in question actually is open but the fault

is still present, attempt to clear the fault by pressing

“RESET.”

If the event does not reset, contact your factory-

authorized service provider.

Byp Overload

Ph A

The critical load is greater than 110% while the

UPS is on bypass. The controls may shut the unit

down if the overload condition does not clear

within the allotted time. Allotted time is variable,

and is inversely proportional to the amplitude of

the overload, i.e., the greater the amplitude of the

overload, the less time the unit continues to

support the load.

This alarm is self-clearing. When the condition is

no longer present, the alarm and any control

activity tied to the alarm reverts to normal.

Press “SILENCE” to silence the audible alarm.

Observe the calculated load percentage on A phase

displayed on the Module Output Meter. If the A

phase steady state load percentage exceeds 110%,

perform the following:

If Maintenance Bypass is available, follow Standard

Operating Procedures to transfer the load to

Maintenance Bypass.

If Maintenance Bypass is not available but the

system has an Internal Bypass Breaker (CB3 on the

One-Line Display), close CB3. Note that depending

on the severity of the overload, the possibility exists

that CB3 could trip if the overload exceeds the

breaker rating.

Investigate the overload condition.

If the Module Output Meter does not indicate an

overload condition, perform the previous steps and

contact your factory-authorized service provider.

Byp Overload

Ph B

The critical load is greater than 110% while the

UPS is on bypass. The controls may shut the unit

down if the overload condition does not clear

within the allotted time. Allotted time is variable,

and is inversely proportional to the amplitude of

the overload, i.e., the greater the amplitude of the

overload, the less time the unit continues to

support the load.

This alarm is self-clearing. When the condition is

no longer present, the alarm and any control

activity tied to the alarm reverts to normal

Press “SILENCE” to silence the audible alarm.

Observe the calculated load percentage on B phase

displayed on the Module Output Meter. If the B

phase steady state load percentage exceeds 110%,

perform the following:

If Maintenance Bypass is available, follow Standard

Operating Procedures to transfer the load to

Maintenance Bypass.

If Maintenance Bypass is not available but the

system has an Internal Bypass Breaker (CB3 on the

One-Line Display), close CB3. Note that depending

on the severity of the overload, the possibility exists

that CB3 could trip if the overload exceeds the

breaker rating.

Investigate the overload condition.

If the Module Output Meter does not indicate an

overload condition, perform the previous steps and

contact your factory-authorized service provider.

Table 7

Liebert NXL alarm and status messages (continued)

Event Message

Event Definition

Recommended Action

Advertising