UPS Alarm and Status Messages

61

Regen Terminated

Regeneration Mode is a service mode that is

normally controlled by the service technician.

Regeneration Mode Status or Alarm messages

are generally intended for the service person.

This status message informs the user that Regen

Mode is no longer active.

This status message is self-clearing. When the

condition is no longer present, the alarm and any

control activity tied to the alarm reverts to normal.

Under normal circumstances, none.

If this message is active, and there is no clear

reason why the UPS was in Regeneration Mode, or

if the command to terminate Regeneration Mode

was not issued, contact your factory-authorized

service provider.

Remote Off BPSS

The Static Bypass Switch (BPSS) was turned off

by an external signal.

This indicates an external signal forcing the BPSS

to remain off is active.

This type of signal is wired into an Input Contact

Isolator and the specific channel is assigned as

Remote Off BPSS.

This status message is self-clearing. When the

condition is no longer present, the message and

any control activity tied to the status event reverts

to normal.

Check the state of the Remote Off BPSS signal.

If this signal is not active, or if no signal wires are

present, contact your factory-authorized service

provider.

Remote Off Inv

The Inverter was turned off by an external signal.

This indicates an external signal forcing the

Inverter to remain off is active.

This type of signal is wired into an Input Contact

Isolator and the specific channel is assigned as

Remote Off Inverter.

This status message is self-clearing. When the

condition is no longer present, the message and

any control activity tied to the status event reverts

to normal.

Check the state of the Remote Off Inverter signal.

If this signal is not active, or if no signal wires are

present, contact your factory-authorized service

provider.

Remote Off Rect

The Rectifier was turned off by an external signal.

This indicates an external signal forcing the

Rectifier to remain off is active.

This type of signal is wired into an Input Contact

Isolator and the specific channel is assigned as

Remote Off Rectifier.

This status message is self-clearing. When the

condition is no longer present, the message and

any control activity tied to the status event reverts

to normal.

Check the state of the Remote Off Rectifier signal.

If this signal is not active, or if no signal wires are

present, contact your factory-authorized service

provider.

REPO Shutdown

The UPS shuts down in response to an active

Remote Emergency Power Off (REPO)

command.

Press “SILENCE” to silence the audible alarm.

Resolve the issue that precipitated the REPO.

For safety, the UPS latches an REPO event. There

are two ways to clear the latch:

1. Press the Reset pushbutton on the External

Interface Board (EIB).

2. From HMI front panel display, press OK button

when ” Press OK to Reset EPO Latched signal”

message is displayed

in a dialog box.

Verify the REPO is cleared by observing the REPO

alarm in the Active Event Window is gone.

Restart the UPS by pressing “Startup,” “Manual

Start,” and follow the prompts.

Restart in Process

Automatic Restart is in progress. This message

clears when the Automatic Restart sequence is

complete.

To complete the Automatic Restart, follow the

prompts on the display.

Restart Inhibited

Automatic Restart of the UPS is not allowed

because of an external signal.

Automatic Restart Inhibit is active when signaled

from an external source. The signal is wired into

Input Contact Interface (ICI 1).

Investigate and resolve the external signal forcing

the UPS to remain off.

If you do not have an ICI, or if there are no external

off signals input to the UPS, contact your factory-

authorized service provider.