UPS Alarm and Status Messages

46

Batt Temp

Imbalance

With more than one Battery Temperature Sensor

installed, the controls are detecting too great a

temperature difference between the individual

sensors.

Press “SILENCE” to silence the audible alarm.

To attempt to identify which sensor is reporting an

inconsistent temperature or an overheating battery,

observe the temperature reading inside the Battery

Box on the One-Line Display. Cycle through all

connected batteries by pressing the Battery Box.

If it appears this alarm is due to a specific cabinet or

battery string being warmer than the others, verify

through investigation whether the string is actually

getting warmer than the others, or if the sensor

appears to be reporting incorrectly.

Contact your factory-authorized service provider.

Batt Test Failed

An Automatic or Manual Battery Test Failed. The

battery “Test Duration” is adjustable. The battery

test fail criteria were met before the end of the

timed battery test.

For example, there must be at least 25% load to

run the battery test. If, during the battery test the

load drops below 25%, the test fails.

Press “SILENCE” to silence the audible alarm.

Contact your factory-authorized service provider.

Batt Test Inhibit

The conditions required to perform an automatic

battery test are not met.

When the battery test is inhibited, the system

delays the test for 7 days. If conditions are

satisfied after 7 days, the UPS performs the

battery test at that time.

Examples of conditions required to run the

automatic battery test are at least 20% load, all

battery breakers closed, normal operation, etc.

Check the Active Event Window and investigate

other events to further analyze.

If there are other active events in the Active Event

Window, press “RESET” to clear the events.

Check the One-Line display to verify the UPS is

online.

Check the Module Output Meter and verify the kW

load is between 20%-100%.

Press the Battery Box on the One-Line Display and

verify all battery strings show at least 90% charged

and all battery breakers are closed.

If the issue cannot be resolved, contact your

factory-authorized service provider.

Batt Test Passed

The Battery Test passed.

None.

BFB Open

The Backfeed Breaker is open.

The Backfeed Breaker feeds the Static Bypass

Switch (BPSS). The physical location of the

breaker depends on unit configuration. It may be

located in the UPS, or it may be located external

to the UPS.

The purpose of the Backfeed Breaker is to

prevent leakage current through the bypass circuit

during an outage.

This status message is self-clearing. When the

condition is no longer present, the message and

any control activity tied to the status event reverts

to normal.

This status message is informational. If the breaker

was not opened intentionally, or if the breaker is

actually closed and this message is active, contact

your factory-authorized service provider.

BPSS Ovld

Exceeded

The Bypass Static Switch (BPSS) was turned off

due to an extended overload.

While the BPSS can sustain an overload greater

than the Inverter and for a longer period of time,

there are still limits on the amplitude and duration

of overload that the BPSS can handle. This alarm

indicates the overload was greater in amplitude

and time than the BPSS can handle, and

therefore shut off to prevent damage to the

equipment.

Press “SILENCE” to silence the audible alarm.

If CB3 is available (visible if present on the One-

Line Display), close it to restore power to the load.

DO NOT ATTEMPT TO CLOSE CB3 UNTIL THE

SOURCE OF THE OVERLOAD IS IDENTIFIED

AND ISOLATED.

Once the overload source is isolated, restart the

UPS by pressing “Startup,” “Manual Start” and

follow the prompts.

If the overload condition does not clear, or the

overload is cleared but the UPS does not restart,

contact your factory-authorized service provider.

BPSS Unable

A problem has been detected in the Bypass Static

Switch.

Press “SILENCE” to silence the audible alarm.

Press “RESET” to attempt to clear the fault.

Contact your factory-authorized service provider.

Table 7

Liebert NXL alarm and status messages (continued)

Event Message

Event Definition

Recommended Action