UPS Alarm and Status Messages

62

Service Code

Active

This event is for informational purposes, and

informs the user that Service Code is currently

running.

This status message is self-clearing. When the

condition is no longer present, the alarm and any

control activity tied to the alarm reverts to normal.

Under normal circumstances, none.

If this message is active, and Service Code is not

loaded, contact your factory-authorized service

provider.

Temp Sense Fail

An equipment temperature sensor is reporting an

invalid temperature. The controls ignore

temperatures from a failed sensor.

Press “SILENCE” to silence the audible alarm.

Press “RESET” to clear the alarm.

If the alarm cannot be reset, or if the alarm condition

returns, contact your factory-authorized service

provider.

Xfer to Byp Failed

An event (such as an Inverter fault) caused an

attempted automatic transfer to bypass and the

transfer failed.

The controls detect the Static Bypass Switch

(BPSS) failed to assume the load and the Inverter

was off.

Press “SILENCE” to silence the audible alarm.

Check the Event Log by pressing “Status Reports,”

“Event Log” to investigate why the UPS tried to

transfer to bypass and why the BPSS failed.

If CB3 is available (as displayed on the One-Line

Display), close CB3 to restore power to the load.

Press “RESET” to attempt to clear any latched

alarms or faults.

If conditions appear normal, attempt to restart the

UPS by pressing “Startup,” “Manual Start” and

follow the prompts.

Contact your factory-authorized service provider.

Table 7

Liebert NXL alarm and status messages (continued)

Event Message

Event Definition

Recommended Action