Emerson 250-400kVA User Manual

Page 60

Advertising
background image

UPS Alarm and Status Messages

54

Input Current Limit

An active Input Current Limit alarm means the

detected input current (RMS) exceeds the limit

setpoint (default is 125%). This may be normal

depending on various operating conditions, such

as input voltage level, output load level, and

whether the batteries have recently discharged.

This alarm is self-clearing. When the condition is

no longer present, the alarm and any control

activity tied to the alarm reverts to normal.

Press “SILENCE” to silence the audible alarm.

Observe the meters on the One-Line Display for

input voltage level, battery charge/discharge

current, and output load percentage kW. Investigate

any abnormal readings.

If the reason for the alarm cannot be determined,

contact your factory-authorized service provider.

Input Disconnect

(Q1) Open

The rectifier disconnect device indicates that it is

in the open position.

Input Disconnect

(Q11) Open

The externally mounted input isolator indicates

that it is in the open position.

Input Filter Cycle

The Input Filter Disconnect is locked open.

The Input Filter Disconnect Cycle counter has

exceeded the setpoint. The Input Filter

Disconnect opens automatically as determined by

the disconnect settings, or because of an unusual

condition.

An example of a setting would be to automatically

open the filter disconnect under light load

conditions to improve the input power factor. An

example of an unusual condition would be

unbalanced currents on the input, possibly

because of a suspect component in the filter itself.

Press “SILENCE” to silence the audible alarm.

Attempt to manually close the disconnect by

pressing “Startup,” “Device Control,” “Close Trap.”

If the condition which caused the filter disconnect to

lock open is still present, it re-opens.

If the disconnect cannot be manually closed or the

alarm cannot be cleared, contact your factory-

authorized service provider.

Input Not Avail

This summary alarm means there is a problem

with input power. It is not acceptable to the

Rectifier.

If the unit is running normally when this event

occurs, the UPS goes to battery.

This alarm is self-clearing. When the condition is

no longer present, the alarm and any control

activity tied to the alarm reverts to normal.

Press “SILENCE” to silence the audible alarm.

Examine the One-Line Display. The Rectifier input

line feeding the Input Breaker should be green. If

not, investigate source power to the UPS.

If input power is good, and this alarm is active,

contact your factory-authorized service provider.

Internal Comm

Error

This is a summary event caused by an

interruption in communication between the

controls and a device on the Controller Area

Network (CAN).

The Internal Communication Error event indicates

a loss of communications between the controls

and an external device.

The Internal Communication Error is displayed

when the controls detect a loss of communication

to a device on the Controller Area Network (CAN).

An infrequent occurrence that resets immediately

is probably not serious.

Press “SILENCE” to silence the audible alarm.

Press “RESET” to clear the alarm.

If the alarm cannot be reset, or if the alarm condition

returns, contact your factory-authorized service

provider.

Inv Overload Ph A

An overload condition is active on A phase.

A phase load condition exceeds 105%.

A countdown timer is displayed on the One-Line

Display in response to this alarm, and indicates

the time remaining until a transfer to bypass

occurs. The length of time remaining until transfer

is directly proportional to the severity of the

overload.

This alarm is self-clearing. When the condition is

no longer present, the alarm and any control

activity tied to the alarm reverts to normal.

Press “SILENCE” to silence the audible alarm.

Check the Module Output Meter and note the A

phase load percentage.

If possible, reduce A phase loading.

If the steady state load remains above 105%, allow

the UPS to transfer to bypass and contact your

factory-authorized service provider.

If the displayed load percentage is less than 100%

and the alarm is still active, contact your factory-

authorized service provider.

Table 7

Liebert NXL alarm and status messages (continued)

Event Message

Event Definition

Recommended Action