Emerson 250-400kVA User Manual

Page 55

Advertising
background image

UPS Alarm and Status Messages

49

Controls

Comm Fail

The Controls Communication Failure event

indicates a loss of communications between the

Controls and Human Machine Interface (HMI).

The Controls Communication Failure event is

displayed when the HMI detects a loss of

communication with Controls on the Controller

Area Network (CAN).

An infrequent occurrence that resets immediately

is probably not serious.

If the alarm does not clear, or if the alarm condition

returns, contact your factory-authorized service

provider.

Controls Reset

Required

This alarm means one or more critical settings

have been changed by user during UPS

operation.

The change(s) will not take effect until after a UPS

Controls reset. This operation should only be

performed by an authorized service personnel.

This alarm is cleared after UPS Controls reset.

Press “SILENCE” to silence the audible alarm.

DC Link

Gnd Fault -

The negative DC Bus has a ground fault.

The UPS controls monitor the DC Bus negative

half for a voltage imbalance caused by current

flow to ground. This fault means excessive

ground current is detected.

In normal operation, with the batteries connected,

the most likely cause of a current path to ground

is a leaking battery.

If your system includes an optional Battery

Ground Fault Monitor, check if the Battery Ground

Fault message is present also.

Press “SILENCE” to silence the audible alarm.

Press “RESET” to clear the fault.

Perform a visual inspection of the batteries. Look for

signs of leaking battery acid or excessively

corroded battery terminals.

If there are no visible signs of defective batteries,

open one Battery Breaker. Press “RESET” and see

if the condition clears. If the condition clears, you

have isolated the problem to that battery string.

If the condition will not clear, repeat the test with

each connected battery string.

Once the location is identified, or if the battery string

tests are inconclusive, contact your factory-

authorized service provider.

DC Link

Gnd Fault +

The positive DC Bus has a ground fault.

The UPS controls monitor the DC Bus positive

half for a voltage imbalance caused by current

flow to ground. This fault means excessive

ground current is detected.

In normal operation, with the batteries connected,

the most likely cause of a current path to ground

is a leaking battery.

If your system includes an optional Battery

Ground Fault Monitor, check if the Battery Ground

Fault message is present also.

Press “SILENCE” to silence the audible alarm.

Press “RESET” to clear the fault.

Perform a visual inspection of the batteries. Look for

signs of leaking battery acid or excessively

corroded battery terminals.

If there are no visible signs of defective batteries,

open one Battery Breaker. Press “RESET” and see

if the condition clears. If the condition clears, you

have isolated the problem to that battery string.

If the condition will not clear, repeat the test with

each connected battery string.

Once the location is identified, or if the battery string

tests are inconclusive, contact your factory-

authorized service provider.

EMO Shutdown

An Emergency Module Off (EMO) command has

been detected.

The EMO signal means the front panel EMO

button was pressed. A Remote EMO would

display the “REMO Shutdown” alarm.

In response to an EMO, the UPS transfers to

Bypass and shuts off.

Press “SILENCE” to silence the audible alarm.

Resolve the issue that precipitated the EMO.

For safety, the UPS latches an EPO event. To clear

the latch, press the EMO Reset pushbutton on the

External Interface Board (EIB).

Verify the EMO is cleared by pressing “RESET” and

observing that the EPO alarm in the Active Event

Window is gone.

Restart the UPS by pressing “Startup,” “Manual

Start,” and follow the prompts.

Table 7

Liebert NXL alarm and status messages (continued)

Event Message

Event Definition

Recommended Action

Advertising