Emerson 250-400kVA User Manual

Page 65

Advertising
background image

UPS Alarm and Status Messages

59

Multiple Fan Fail

This summary event is active when more than

one fan has failed.

Press “SILENCE” to silence the audible alarm.

Press “RESET” to clear the alarm.

If the alarm will not clear, contact your factory-

authorized service provider.

On Gen Active

The UPS input source is generator.

An external signal is being used to inform the

UPS when the power source is generator rather

than utility, and the signal is active.

This status message is self-clearing. When the

condition is no longer present, the message and

any control activity tied to the status event reverts

to normal.

Under normal conditions, no user action is required.

If the UPS is not actually on generator and this

message is active, contact your factory-authorized

service provider.

Outlet Ovtemp

Limit

The difference between the inlet air temperature

and the outlet air temperature is too great.

This alarm means excessive heat is being

generated internally resulting in a higher than

normal exhaust air temperature.

If the Bypass is within limits, the UPS reacts to

this alarm by transferring to Bypass and shutting

off the Inverter.

This alarm is self-clearing. When the condition is

no longer present, the alarm and any control

activity tied to the alarm reverts to normal.

Press “SILENCE” to silence the audible alarm.

Check the Inlet Air Temperature on the One-Line

Display and verify the reading is accurate, i.e. is the

room temperature warmer than normal?

If the room temperature is warmer than normal,

investigate and resolve the issue.

If the room temperature is normal, and the Inlet Air

Temp reading on the One-Line Display is higher

than normal, contact your factory-authorized service

provider.

Output Fault

This summary event occurs when the detected

system output exceeds acceptable limits in either

voltage or frequency.

If the UPS was on Inverter at the time of the

event, the UPS transfers to bypass provided the

bypass voltage is available.

If the UPS was on bypass at the time of the event,

the UPS shuts down rather than allowing

unacceptable voltage to reach the load.

Press “SILENCE” to silence the audible alarm.

Check the Active Event Window and investigate

other events to further analyze.

Press “RESET” to attempt to reset any latched

events.

Check the One-Line Display to determine the

system status (on UPS, Bypass, or Off).

Check the input and bypass (dual input only) and

observe the One-Line color. Green indicates good

power present, orange means power is present but

outside nominal range, and gray means power is

not present.

If the load is off and the input voltage is ok, attempt

to restart the UPS by pressing “Startup,” “Manual

Start,” and follow the prompts.

If the Input Meter indicates input or bypass is not

available, investigate and resolve the power

problem.

If the load is on bypass and all alarms are reset,

press “Transfer,” “UPS,” to attempt to transfer back

to Inverter.

If the issue cannot be resolved, contact your

factory-authorized service provider.

Table 7

Liebert NXL alarm and status messages (continued)

Event Message

Event Definition

Recommended Action

Advertising