Emerson 250-400kVA User Manual

Page 61

Advertising
background image

UPS Alarm and Status Messages

55

Inv Overload Ph B

An overload condition is active on B phase.

B phase load condition exceeds 105%.

A countdown timer is displayed on the One-Line

Display in response to this alarm, and indicates

the time remaining until a transfer to bypass

occurs. The length of time remaining until transfer

is directly proportional to the severity of the

overload.

This alarm is self-clearing. When the condition is

no longer present, the alarm and any control

activity tied to the alarm reverts to normal.

Press “SILENCE” to silence the audible alarm.

Check the Module Output Meter and note the B

phase load percentage.

If possible, reduce B phase loading.

If the steady state load remains above 105%, allow

the UPS to transfer to bypass and contact your

factory-authorized service provider.

If the displayed load percentage is less than 100%

and the alarm is still active, contact your factory-

authorized service provider.

Inv Overload Ph C

An overload condition is active on C phase.

C phase load condition exceeds 105%.

A countdown timer is displayed on the One-Line

Display in response to this alarm, and indicates

the time remaining until a transfer to bypass

occurs. The length of time remaining until transfer

is inversely proportional to the severity of the

overload.

This alarm is self-clearing. When the condition is

no longer present, the alarm and any control

activity tied to the alarm reverts to normal.

Press “SILENCE” to silence the audible alarm.

Check the Module Output Meter and note the C

phase load percentage.

If possible, reduce C phase loading.

If the steady state load remains above 105%, allow

the UPS to transfer to bypass and contact your

factory-authorized service provider.

If the displayed load percentage is less than 100%

and the alarm is still active, contact your factory-

authorized service provider.

Inv Ovld Exceeded

This message is displayed in response to an

overload on one or more output phases.

When an overload occurs, the controls display a

countdown timer that displays the time remaining

until a transfer to bypass occurs. The length of the

timer is inversely proportional to the amplitude of

the overload. When the timer reaches zero, the

UPS transfers to bypass and populates the Active

Event Window with this alarm.

This fault is non-latching. When the underlying

condition is no longer present, this fault and any

control activity tied directly to this fault reverts to

normal.

Press “SILENCE” to silence the audible alarm.

Observe the load percentages for each phase on

the Module Output Meter. If the load is less than

100%, attempt to transfer back to Inverter by

pressing “Transfer,” “UPS.”

If the transfer is successful, investigate the reason

for the overload and take appropriate action.

If the transfer is unsuccessful, contact your factory-

authorized service provider.

Inverter Fault

This summary event indicates a potentially

serious problem in the Inverter.

The controls react to an Inverter fault in different

ways depending on the root event that caused the

fault. If bypass is available, the controls transfer to

static bypass.

A restart may or may not be possible

Press “SILENCE” to silence the audible alarm.

Check the One-Line Display to determine the state

of the UPS. If both the Rectifier and Inverter are

shut off, press “RESET” to attempt to clear any

latched alarms or faults.

Attempt a restart by pressing “Startup,” “Manual

Start,” and follow the prompts to place the UPS

back in service.

If the startup fails, contact your factory-authorized

service provider.

If the Rectifier and Inverter appear to be running,

press “RESET” to attempt to clear any latched

alarms or faults, then attempt a transfer by pressing

“Transfer,” “UPS.” If the transfer is successful,

contact your factory-authorized service provider.

If the transfer is unsuccessful, contact your factory-

authorized service provider.

ISS SCR Shorted

The controls have detected voltage on the

Inverter (Line side) side of the Inverter Static

Switch.

This indicates that an SCR is shorted.

With the Output SCRs turned off, there should be

no voltage present inside the UPS.

This is a non-recoverable fault, and inhibits

normal start up of the UPS.

Press “SILENCE” to silence the audible alarm.

Turn off Control Power to clear the event. Wait 5

minutes before re-applying Control Power.

If the fault fails to clear, contact your factory-

authorized service representative.

Table 7

Liebert NXL alarm and status messages (continued)

Event Message

Event Definition

Recommended Action

Advertising