UPS Alarm and Status Messages

51

Equip

Ovtemp

Limit

This summary event occurs when one or more

internal temperatures have exceeded the

maximum temperature setpoint. This is the

second of two over temperature alarms. The first,

“Equipment Overtemperature Warning,” sets

when the detected temperature is near the limit.

The controls react to this condition in various

ways, depending on which sensor is reporting the

over temperature condition.

Press “SILENCE” to silence the audible alarm.

Check the One-Line Display for system status:

1. UPS Off

a. If external Maintenance Bypass is available,

close the Maintenance Bypass Breaker

(MBB) to restore power to the load. Do not

attempt to restart the UPS without first

contacting your factory-authorized service

provider.

b. If external Maintenance Bypass is not

available, but the CB3 option is visible on the

One-Line Display, verify the bypass line is

green and close CB3 to restore power to the

load. Contact your factory-authorized

service provider.

2. UPS On Bypass

a. Verify the bypass line is green. If it is not,

contact your factory-authorized service

provider immediately and prepare to shut

down the load.

b. If external Maintenance Bypass is available,

close the Maintenance Bypass Breaker

(MBB) to place the load on Maintenance

Bypass. Do not attempt to re-transfer to UPS

without first contacting your factory-

authorized service provider.

c. If external Maintenance Bypass is not

available, but the CB3 option is visible on the

One-Line Display, close CB3. Do not

attempt to re-transfer to UPS without first

contacting your factory-authorized service

provider.

3. UPS On Battery

a. Verify the bypass line is green. If it is not,

contact your factory-authorized service

provider immediately and prepare to shut

down the load.

b. If the bypass line is green, press "Transfer",

"Bypass", to transfer the load to bypass.

c. If there is a CB3 present on the One-Line

Display, close CB3. If CB3 is not present

and external Maintenance Bypass is

available, close the MBB to place the load

on Maintenance Bypass. If both CB3 and

Maintenance Bypass are present, first close

CB3, then close the external MBB. If CB3 or

external Maintenance Bypass is not

available, shut down the UPS by pressing

"Shutdown", "UPS" and contact your factory-

authorized service provider.

Table 7

Liebert NXL alarm and status messages (continued)

Event Message

Event Definition

Recommended Action