UPS Alarm and Status Messages

50

EPO Shutdown

The UPS shuts down in response to an active

Emergency Power Off (EPO) command.

Press “SILENCE” to silence the audible alarm.

Resolve the issue that precipitated the EPO.

For safety, the UPS latches an EPO event. There

are two ways to clear the latch:

1. Press the EPO Reset pushbutton on the External

Interface Board (EIB).

2. From HMI front panel display, press OK button

when ” Press OK to Reset EPO Latched signal”

message is displayed

in a dialog box.

Verify the EPO is cleared by observing the EPO

alarm in the Active Event Window is gone.

Restart the UPS by pressing “Startup,” “Manual

Start,” and follow the prompts.

Equip Ovtemp

This summary event indicates the UPS is nearing

an over temperature condition. Depending on

which sensor is reporting the high temperature,

the UPS may do one of three things once the limit

is reached: shut down, transfer to bypass, or

transfer to battery operation. This is a potentially

serious event.

Investigate possible causes for a rising temperature

condition, such as loss of air conditioning, airflow

obstructions, etc. If the ambient temperature is high

due to loss of air conditioning and cannot be

addressed immediately, perform the following:

1. Press “Transfer,” “Bypass” to transfer the UPS

to bypass.

2. Press “SILENCE” to silence the audible alarm.

3. Wait at least 15 minutes, then attempt to reset

the alarm by pressing “RESET.”

4. If the alarm clears and proper cooling has been

restored to the UPS, press “Transfer,” “UPS” to

transfer back to UPS.

If this alarm is present and no external factors are

affecting proper cooling of the UPS, contact your

factory-authorized service provider.