UPS Alarm and Status Messages

45

Batt Ovtemp Limit

One or more of the Battery Temperature Sensors

is reporting a temperature above the limit

setpoint.

There are two user-adjustable Battery

Temperature Setpoints: Battery Over

Temperature Warning and Battery

Overtemperature Limit. The temperature in one or

more battery compartments has risen above the

limit setpoint.

Depending on user settings, the controls may trip

the battery breaker associated with the over

temperature condition.

Press “SILENCE” to silence the audible alarm.

Observe the One-Line Display. To identify which

battery cabinet is reporting the temperature

condition, press the “Battery Box” on the One-Line

Display to cycle through each battery compartment

or string. The temperature display is located under

the voltage reading in the Battery Box.

If the Common Battery Disconnect and/or the

individual battery cabinet or string reporting the over

temperature condition is tripped, check the following

settings.

Press “User Settings,” “Battery Management,”

“Battery Temperature” to check the current Battery

Temperature Setpoints. If none of the Battery Boxes

on the One-Line Display exhibit a temperature in

excess of the temperature setpoint in the user

settings, contact your factory-authorized service

provider.

If the overtemperature limit is being reported

correctly, investigate potential causes such as faulty

air conditioning, or air flow blockage and resolve.

Otherwise, contact your factory-authorized service

provider.

Batt Ovtemp

Warning

One or more of the Battery Temperature Sensors

is reporting a temperature above the warning

setpoint.

There are two user adjustable Battery

Temperature Setpoints: Battery Over

Temperature Warning and Battery

Overtemperature Limit. This alarm means the

temperature in one or more battery compartments

has risen above the warning setpoint.

This alarm is self-clearing. When the condition is

no longer present, the alarm and any control

activity tied to the alarm reverts to normal

Press “SILENCE” to silence the audible alarm.

Observe the One-Line Display. To identify which

battery cabinet is reporting the temperature

condition, press the “Battery Box” on the One-Line

Display to cycle through each battery compartment

or string. The temperature display is located under

the voltage reading in the Battery Box.

Press “User Settings,” “Battery Management,”

“Battery Temperature” to check the current Battery

Temperature Setpoints. If none of the Battery Boxes

on the One-Line Display exhibit a temperature in

excess of the temperature setpoint in the user

settings, contact your factory-authorized service

provider.

If the overtemperature warning is being reported

correctly, investigate potential causes, such as

faulty air conditioning or air flow blockage and

resolve. Otherwise, contact your factory-authorized

service provider.

Batt Self Test

The UPS is performing a battery self test.

The battery self test terminates automatically at

the end of the test.

Battery test settings are adjustable and can be

accessed by pressing “Config,” “User Settings,”

“Batt Mgt,” “Battery Test.”

This status message is self-clearing. When the

condition is no longer present, the message and

any control activity tied to the status event reverts

to normal.

During normal operation, no user response is

required.

The battery test can be terminated at any time by

the user by pressing “Batt Mgt,” “Manual Battery

Test,” “Stop.”

Batt Sensor Fail

The controls are sensing a failed Battery

Temperature Sensor.

If a sensor reports a value outside the normal

operating range of the sensor, it is considered

failed.

This alarm is self-clearing. When the condition is

no longer present, the alarm and any control

activity tied to the alarm reverts to normal.

Press “SILENCE” to silence the audible alarm.

Try to identify which sensor has failed by observing

the temperature reading inside the Battery Box on

the One-Line Display. Cycle through all connected

batteries by pressing the Battery Box on the display.

Contact your factory-authorized service provider.

Table 7

Liebert NXL alarm and status messages (continued)

Event Message

Event Definition

Recommended Action

Advertising