UPS Alarm and Status Messages

53

Inp Phase Rotation

The correct input phase rotation should be

clockwise, or A-B-C. This alarm indicates the

sensed input phase rotation is counter-clockwise.

If this alarm occurs on an operational unit, it

typically indicates upstream work was performed

(input side) and the input wiring was connected

incorrectly.

This alarm is self-clearing. When the condition is

no longer present, the alarm and any control

activity tied to the alarm reverts to normal.

Press “SILENCE” to silence the audible alarm.

Verify correct phase rotation at the input.

If the phase rotation is correct, contact your factory-

authorized service provider.

Input Contact XY

The displayed text for this alarm is dependent on

settings.

In response to this alarm, the user may see 1 of 4

possible messages:

1. No message but the help icon (lowercase “i“)

is present;

2. A custom message programmed by the user;

3. “Input Contact XY” if the contact is

unconfigured;

4. “Reduced Rect ILimit” if the contact is

programmed as Pre-assigned.

If this event is active, an external signal is wired

into Channel Y of Input Contact Isolator #X.

If the display shows Case 1 above (blank

message), it means the contact channel is set to

default but the default message was erased.

If the display shows Case 2, the user-

programmed event is active and the displayed

text is customer defined.

If the display shows Case 3, the contact is active

but was not pre-programmed (default condition).

If the display shows Case 4, the controls force the

Rectifier into Reduced Input Current Limit

operation (this limits the amount of current

available to charge the battery - typically during

generator operation).

This alarm message is self-clearing. When the

condition is no longer present, the message and

any control activity tied to the alarm will revert to

normal.

Check the wires landed on Input Contact

Isolator #X.

If the signal is not active, or no wires are present,

contact your factory-authorized service provider.

Input Contact

Interface #1

Communication

Failure

Input Contact Interface #1 has failed to

communicate in a timely fashon.

Input Contact

Interface #2

Communication

Failure

Input Contact Interface #2 has failed to

communicate in a timely fashon.

Input Current

Imbal

The detected input currents are not balanced.

This latching alarm indicates a potential problem

in the input filter. The controls automatically open

the filter contactor in response to this condition.

The filter contactor must be manually closed once

it opens in response to this alarm.

Press “SILENCE” to silence the audible alarm.

Press “RESET” to attempt to clear the alarm

condition.

If the alarm clears, press “Startup,” “Device

Control,” “Close Trap” to manually close the filter

contactor.

If the contactor remains closed, check the Input

Meter and verify the input currents are balanced.

If the contactor re-opens and the “Input Current

Imbalance” returns, silence the alarm, leave the

filter contactor open, and contact your factory-

authorized service provider.

Table 7

Liebert NXL alarm and status messages (continued)

Event Message

Event Definition

Recommended Action