INSTALLATION AND USE MANUAL

Chapter 4

page

24

Installation and assembly

Technical service – MCZ GROUP S.p.A. all rights reserved - Reproduction prohibited

4.6.2. Hydraulic connection with Open Tank

In order to achieve a good running of the Hydrotherm fireplace stove

installed with open tank, please closely follow the installation rules

stated below:

 The system must be loaded only by natural fall from the

expansion tank open in the del return of the fireplace stove

with a duct of 1”. Direct loading with the pressure from the

mains is prohibited. The maximum operating pressure is 1.5

bars.

 The expansion tank must be of the open type with vent tube of

minimum Ø 1”. This must be placed at a height higher than 3

meters from the highest point of the radiators. If the kits in

diagrams 2 and 3 are used, the expansion tank can be

placed near the fireplace stove.

 The vent tube of the expansion tank must feature no shut-off

valve or unneeded curves. Both the open expansion tank and

the vent tube must be protected against the cold.

4.6.3. Hydraulic connection with Closed Tank

In order to achieve a good running of the Hydrotherm fireplace stove

installed with closed tank, please closely follow the installation rules

stated below:

The system must be loaded only with the pressure from

the mains. The maximum operating pressure is 1.5 bars.

The expansion tank must be of the closed type.