background image

9

4-2-7 IDLE CONTROL UNIT

(RGV12100 only)

The idle control unit

1

1

releases throttle

valve when the applied load current exceeds
0.04A.
The two output wires

2

2

from the main coils

must go through the ZCT

3

3

in the same

direction.

NOTE :
It is normal that the engine speed goes up for
a moment when you turn the key switch to
"STOP" while the Idle Control Switch is in
"ON" position.

1

2

3

Function

Description of Operation

Fail-safe function

When the key switch or the remote control switch is turned to "START", the
fuel cut-off valve of the carburetor opens. When the key switch or the
remote control switch is turned to "STOP", the fuel cut-off valve closes.

If the starter motor is locked by any reason, the starter motor is shut off
automatically after 3 seconds.

When the engine dose not start (engine speed does not reach 1,050
r/min), the starter motor is stopped after 21 seconds.

When the remote controller is connected, the electric starter dose not run
when the switch of remote controller is turned "OFF" even if the key switch
on the generator is turned to "START".

When the engine speed increases higher than 4,500 r/min for 7 seconds,
the engine is shut down automatically and the warning lamp repeats turn-
ing on and off for 3 minutes.

Self checking function for
warning lamp bulb

When the key switch or remote control switch is turned to "START", the
warning lamp lights up for a moment to indicate that the bulb for the warn-
ing lamp is normal.