2 compressor control, Compressor proportional bands, Compressor control – Emerson Liebert iCOM User Manual

Page 24: Two-step)

Advertising
background image

Operation

18

3.3.2 Compressor Control

Depending on the type of Liebert air conditioning unit you have your unit may contain one or two

compressors with or without unloaders.

Compressor Proportional Bands

One Single-Step Compressor Without Unloaders—One-Step
One single-step compressor, Cool 1, is started at 100% call for cooling from the temperature propor-

tional band and stopped at 0% (see Figure 12).

Figure 12 One single-step compressor without unloaders

Two Single-Step Compressors Without Unloaders—Two-Step
First single-step compressor, Cool 1, is started at 50% calculated output from the temperature propor-

tional band, and stopped at 0%. The second compressor, Cool 2, starts at 100% and stops at 50% (see

Figure 13).
One Compressor With an Unloader—Two-Step
The two-step compressor is started unloaded at 50%, Cool 1, calculated output from the temperature

proportional band and stopped at 0%. At 100% the compressor starts fully loaded, Cool 2, and returns

to unload operation at 50% (see Figure 13).

Figure 13 Two single-step compressors without unloaders or one compressor with an unloader (two-step)

Temp Setpoint : 70°F
Proportional Band : 8°F
Deadband : 2°F

75

½ Proportional Band

0%

Cooling

+ 100 %

Cooling

71

72

73

74

70

½ Dead-

band

Cool 1

Off

Cool 1

On

Increasing Temperature

Temp Setpoint : 70°F
Proportional Band: 8°F
Deadband : 2°F

75

1/2 Proportional Band

0%

Cooling

+ 100%

Cooling

71

72

73

74

70

1/2 Dead-

band

Cool 1

On

Cool 2

On

Increasing Temperature

Cool 2

Off

Cool 1

Off