0 user menu parameters, Table 12 setpoints parameters, Spare part list—large display only – Emerson Liebert iCOM User Manual

Page 57: Table 14 event log parameters, Arameters, Table 12, Setpoints parameters, Table 13, Spare part list parameters—large display only, Table 14

Advertising
background image

User Menu Parameters

51

7.0

U

SER

M

ENU

P

ARAMETERS

User menus report general cooling unit operations and status. The password for the user menu is

1490.
The iCOM control firmware is being updated constantly. As a result, the User menu parameter tables

in this manual may be slightly different than what is shown on your cooling unit's display. Please

check

www.liebert.com

for the latest iCOM User manual updates.

Spare Part List—Large Display Only

Displays the various Liebert part numbers for all parts in the cooling unit to simplify ordering

replacement parts.

Table 12

Setpoints parameters

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

Page 1 of 1
Password

PASSWORD

W

-

Temperature Setpoint

TEMP SET

W

41-104°F (5-40°C)

Humidity Setpoint

HUM SET

W

20-80%

(settings lower than 19%

will be forced to 20)

Humidity Control Type

HUM CTRL

W

Relative, Compensated,

Predictive

Supply Limit

SUP LIM

W

Enabled, Disabled

Supply Limit Temp Value

SUP TEMP

W

41-77°F (5-25°C)

Backup Temperature

Setpoint

BACK TPS

W

41-104°F (5-40°C)

Table 13

Spare part list parameters—large display only

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

Page 1 of 1
List of parts

N/A

R

-

Table 14

Event log parameters

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

Page 1 of 1
Last 400 events

Last 400 events

R

-

Table 15

View network parameters—large display only*

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

Page 1 of 1

Status Unit 1—32

N/A

R

AlarmOff, Manual, LocalOff, SystemOff,

AlarmStandby, Standby, TimerOff,

SystemOn, WarningOn, AlarmOn, Timer

* Permits viewing all units connected in a network. Viewable on a large display only.

°C / °F

% RH

SET

EVENT

LOG

Advertising