Service Menu Parameters

73

Table 32

Options setup parameters

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

Page 1 of 3
Password

PASSWORD

W

-

Compressor Sequence

COMP SEQ

R

Auto, 1, 2

Low Pressure Alarm Delay

LP DELAY

W

0-5 min

Electric Stages

EL HEAT

W

0, 1, 2, 3

Hot Water Heat On/Off

HW HEAT

W

No, Yes

Total Heat Stages

ALL HEAT

R

0, 1, 2, 3

LWD Connected

LWDconn

W

No, Yes

3P Actuator Runtime

3P RUN

W

30-500 sec

3P Actuator Direction

3P DIR

W

Direct, Reverse

Page 2 of 3
Password

PASSWORD

W

-

Humidification Enabled

HUM ENAB

W

No, Yes

Infrared Flush Rate

IR FLUSH

W

110-500%

Humidifier Steam Rate

HUM STEAM

W

No, Yes

Humidifier Bottle Flush Time

HumFlush

W

5-30 sec

Humidifier Bottle Manual Flush

ManFlush

V

Yes, No

Auto Restart Enabled

REST EN

W

Yes, No

Single Unit Auto Restart

RESTART

W

0-999 sec

On-Off Enabled

ONOFF EN

W

Yes, No

Page 3 of 3
CW Flush

CW FLUSH

W

0-99 hours

Freecooling Flush

FC FLUSH

W

0-99 hours

Hot Water Flush

HW FLUSH

W

0-99 hours

Ball Valve Setpoint Offset

BALL OFF

W

-1.8 / 3.5 bar

(-26 / +51 psi)