Table 29 sensor calibration / setup parameters, Table 29, Sensor calibration / setup parameters – Emerson Liebert iCOM User Manual

Page 75

Advertising
background image

Service Menu Parameters

69

TYPE

-

-

-

COMP 1 SHORT CYCLE

SC1

W

MSG, WRN, ALM

COMP 2 SHORT CYCLE

SC2

W

MSG, WRN, ALM

NO POWER

NOP

W

MSG, WRN, ALM

CONDENSER 1 FAILURE

CN1

W

MSG, WRN, ALM

CONDENSER 2 FAILURE

CN2

W

MSG, WRN, ALM

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Table 29

Sensor calibration / setup parameters

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

Page 1 of 3
Password

PASSWORD

W

-

Return Temperature

RTN TEMP

W

±18°F (±9.9°C)

Calibrated Return Temperature

CAL TEMP

R

32-122°F (0-50°C)

Return Humidity

RTN HUM

W

±9.9%

Calibrated Return Humidity

CAL HUM

R

20-80%

Digiscroll 1 NTC

DS1 NTC

W

±18°F (±9.9°C)

Calibrated Digiscroll 1 NTC

CAL DS1

R

84-313°F (29-156°C)

Digiscroll 2 NTC

DS2 NTC

W

±18°F (±9.9°C)

Calibrated Digiscroll 2 NTC

CAL DS2

R

84-313°F (29-156°C)

Page 2 of 3
Password

PASSWORD

W

-

Temperature Sensor A

TEMP A

W

±18°F (±9.9°C)

Calibrated Temperature Sensor A

CAL A

R

32-122°F (0-50°C)

Humidity Sensor A

HUM A

W

±9.9%

Calibrated Humidity Sensor A

CAL A

R

20-80%

Temperature Sensor B

TEMP B

W

±18°F (±9.9°C)

Calibrated Temperature Sensor B

CAL B

R

32-122°F (0-50°C)

Humidity Sensor B

HUM B

W

±9.9%

Calibrated Humidity Sensor B

CAL B

R

20-80%

Page 3 of 3
Password

PASSWORD

W

-

Table 28

Set alarms parameters (continued)

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

SET

ALARMS

+ / -