Table 30 – Emerson Liebert iCOM User Manual

Page 76

Advertising
background image

Service Menu Parameters

70

Freecool Sensor PTC or NTC

FC SNSR

W

PTC, NTC

Freecool Sensor

FC SNSR

W

±18°F (±9.9°C)

Calibrated Freecool Sensor

CAL FC

R

4-113°F (-15 to 45°C)

Supply Sensor PTC or NTC

SUP SNSR

W

PTC, NTC

Supply Sensor

SUP TEMP

W

±18°F (±9.9°C)

Calibrated Supply Sensor

CAL SUP

R

32-122°F (0-50°C)

Temperature Sensor C

TEMP C

W

±18°F (±9.9°C)

Calibrated Temperature Sensor C

CAL C

R

32-122°F (0-50°C)

Humidity Sensor C

HUM C

W

±9.9%

Calibrated Humidity Sensor C

CAL C

R

20-80%

Table 30

System / network setup parameters—large display only

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

Page 1 of 2
Password

PASSWORD

W

-

Number of Connected

Units

W

1-32

Teamwork Mode

W

No, 1, 2

Configuration Safe

R

Not Available, Invalid, OK,

Changed, Updating

Configuration Safe

W

No, SaveLoad

Network Safe

R

Not Available, Invalid, OK,

Changed, Updating

Network Safe

W

No, Save, Load

SW Version

W

Page 2 of 2
Password

PASSWORD

W

-

IP Address

W

IP Range

Table 29

Sensor calibration / setup parameters

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

+ / -

NETWORK