Table 16 set alarms parameters, Table 17 sensor data, Table 16 – Emerson Liebert iCOM User Manual

Page 58: Sensor data, Table 17, Set alarms parameters

Advertising
background image

User Menu Parameters

52

Table 16

Set alarms parameters

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

Page 1 of 1
Password

PASSWORD

W

-

Return Sensor Alarms

RTN SNSR

W

Enabled, Disabled

High Return Temperature

HI TEMP

W

34-210°F (1-99°C)

Low Return Temperature

LO TEMP

W

34-210°F (1-99°C)

High Return Humidity

HI HUM

W

1-99%

Low Return Humidity

LOW HUM

W

1-99%

Sensor A Alarms

SENSOR A

W

Enabled, Disabled

High Temperature Sensor A

HI TEMP A

W

34-210°F (1-99°C)

Low Temperature Sensor A

LO TEMP A

W

34-210°F (1-99°C)

High Humidity Sensor A

HI HUM A

W

1-99%

Low Humidity Sensor A

LO HUM A

W

1-99%

Table 17

Sensor data

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

Page 1 of 2

Optional Sensor A Temperature

TEMP A

R

32-122°F (0-50°C)

Optional Sensor A Humidity

HUM A

R

20-80%

Optional Sensor B Temperature

TEMP B

R

32-122°F (0-50°C)

Optional Sensor B Humidity

HUM B

R

20-80%

Optional Sensor C Temperature

TEMP C

R

32-122°F (0-50°C)

Optional Sensor C Humidity

HUM C

R

20-80%

Freecooling Fluid Temperature

FC TEMP

R

4-113°F (-15 to 45°C)

Outdoor Temperature

AMB TEMP

R

4-113°F (-15 to 45°C)

Freecooling Status

FC STATE

R

Off, Start, On, Blank

DigiScroll 1 Temperature

DS1 TEMP

R

84-313°F (29-156°C)

DigiScroll 2 Temperature

DS2 TEMP

R

84-313°F (29-156 °C)

Page 2 of 2
Daily High Temperature

Hi Temp

R

32-122°F (0-50°C)

Daily High Temperature

Hi Te H

Hi Te M

Hi Te S

R

-

Daily Low Temperature

Lo Temp

R

32-122°F (0-50°C)

Daily Low Temperature

Lo Te H

Lo Te M

Lo Te S

R

-

Daily High Humidity

Hi Humi

R

20-80%

Daily High Humidity

Hi Hu H

Hi Hu M

Hi Hu S

R

-

SET

ALARMS