Emerson Liebert iCOM User Manual

Page 32

Advertising
background image

Operation

26

Standard Mode
In Standard mode, the SCR reheat operates only when the Temperature Proportional Band calls for

heating. SCR reheat output is adjusted proportionally as the Temperature Proportional Band varies

the requirement for heating from 0% to -100%. Compressors operate only when there is a call for cool-

ing as described in 3.3.2 - Compressor Control.
Figure 21 illustrates how SCR reheat operates when SCR Control Type is set to Standard mode.

Figure 21 Two single-step compressors with SCR reheat set to Standard mode

Temp Setpoint : 70°F
Proportional Band : 8°F
Deadband : 0°F

Cool 2

On

Cool 1

On

Cool 2

Off

Cool 1 Off

SCR Off

SCR

On

0%

100 %

Cooling

-100%

Heating

74

71

72

73

66

67

68

69

70

½ Proportional Band

Cooling 1 On

Cooling 2 On

½ Proportional Band

SCR On