Table 28 set alarms parameters, Table 28, Set alarms parameters – Emerson Liebert iCOM User Manual

Page 69

Advertising
background image

Service Menu Parameters

63

Page 7of 7
Status Humidifier Problem

HUM PROB

R

OK, Act

Status DT1 (Outdoor/Glycol)

DT1

R

OK, Act

Status DT2 (Glycol/Room)

DT2

R

OK, Act

Status DT3 (Room/Setpoint)

DT3

R

OK, Act

Status Min CW

MIN CW

R

OK, Act

LWD Value

LWD Val

R

Off, On

Status LSI

LSI

R

Off, On

Table 28

Set alarms parameters

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

Page 1 of 7
Password

PASSWORD

W

-

Return Sensor Alarms

RTN SNSR

W

Disabled, Enabled

High Return Temperature

HI TEMP

W

34-210°F (1-99°C)

Low Return Temperature

LO TEMP

W

34-210°F (1-99°C)

High Return Humidity

HI HUM

W

1-99%

Low Return Humidity

LOW HUM

W

1-99%

Sensor A Alarms

SENSOR A

W

Disabled, Enabled

High Temperature Sensor A

HI TEMPA

W

34-210°F (1-99°C)

Low Temperature Sensor A

LO TEMPA

W

34-210°F (1-99°C)

High Humidity Sensor A

HI HUM A

W

1-99%

Low Humidity Sensor A

LO HUM A

W

1-99%

Table 27

Diagnostics / service mode parameters (continued)

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

SERVICE

SET

ALARMS