Service Menu Parameters

66

ENABLE - DISAB

-

-

-

COMP 1 OVERLOAD

OL1

W

Disabled, Enabled

COMP 2 OVERLOAD

OL2

W

Disabled, Enabled

COMP 1 HIGH PRESSURE

HP1

W

Disabled, Enabled

COMP 2 HIGH PRESSURE

HP2

W

Disabled, Enabled

COMP 1 LOW PRESSURE

LP1

W

Disabled, Enabled

COMP 2 LOW PRESSURE

LP2

W

Disabled, Enabled

COMP 1 PUMPDOWN FAIL

PD1

W

Disabled, Enabled

COMP 2 PUMPDOWN FAIL

PD2

W

Disabled, Enabled

DIG SCROLL1 HIGH TEMP

HT1

W

Disabled, Enabled

DIG SCROLL2 HIGH TEMP

HT2

W

Disabled, Enabled

EL HEAT HIGH TEMP

EHO

W

Disabled, Enabled

TYPE

-

-

-

COMP 1 OVERLOAD

OL1

W

MSG, WRN, ALM

COMP 2 OVERLOAD

OL2

W

MSG, WRN, ALM

COMP 1 HIGH PRESSURE

HP1

W

MSG, WRN, ALM

COMP 2 HIGH PRESSURE

HP2

W

MSG, WRN, ALM

COMP 1 LOW PRESSURE

LP1

W

MSG, WRN, ALM

COMP 2 LOW PRESSURE

LP2

W

MSG, WRN, ALM

COMP 1 PUMPDOWN FAIL

PD1

W

MSG, WRN, ALM

COMP 2 PUMPDOWN FAIL

PD2

W

MSG, WRN, ALM

DIG SCROLL1 HIGH TEMP

HT1

W

MSG, WRN, ALM

DIG SCROLL2 HIGH TEMP

HT2

W

MSG, WRN, ALM

EL HEAT HIGH TEMP

EHO

W

MSG, WRN, ALM

Page 5 of 7
PASSWORD

-

W

-

DELAY

-

-

-

WORKING HRS EXCEEDED

WHE

W

0 - 9999 sec

SMOKE DETECTED

SMO

W

0 - 9999 sec

WATER UNDER FLOOR

WUF

W

0 - 9999 sec

COND PUMP-HIGH WATER

CPH

W

0 - 9999 sec

LOSS OF FLOW

LOF

W

0 - 9999 sec

STBY GLYCOL PUMP ON

SGP

W

0 - 9999 sec

STANDBY UNIT ON

STB

W

0 - 9999 sec

HUMIDIFIER PROBLEM

HUP

W

0 - 9999 sec

NO CONNECTION w/Unit1

NOC

W

internal

UNIT X DISCONNECTED

-

W

internal

LOSS OF POWER

LOP

W

internal

ENABLE - DISAB

-

-

-

WORKING HRS EXCEEDED

WHE

W

Disabled, Enabled

SMOKE DETECTED

SMO

W

Disabled, Enabled

WATER UNDER FLOOR

WUF

W

Disabled, Enabled

Table 28

Set alarms parameters (continued)

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

SET

ALARMS