Installing a Liebert iCOM Unit-to-Unit Network

47

Figure 29 Liebert iCOM input-output control board

Liebert vNSA

The Liebert vNSA is designed to connect multiple Liebert iCOM control devices. The Liebert vNSA

contains either one or two powered industrial rail switches. An optional remote large display can be

attached to the front door as well. All models have a power supply that requires connection to a single

phase 120V or 240VAC power source. The enclosure features a key lock for security.
The Liebert vNSA supports autonegotiation, autopolarity and autocrossing, allowing for the use of

standard network cables for connection to each port, rather than special crossover cables. The switch

detects and makes adjustments for the network's speed and transmission mode, polarity and trans-

mit-and-receive pins. See the Liebert vNSA user manual, SL-18840, for more details.
The number of ports available for connecting Liebert iCOM control devices varies by model as shown

in Table 11. Models with a remote large display attached to the front door utilize one of the available

Ethernet ports in the Liebert vNSA. Models with two switches utilize two ports to connect the

switches.
Table 11

Ports available for connecting Liebert iCOM control devices

Model

Liebert

vNSA With

Remote

Large

Display

Total Number

of Ports

Number of Ports

Used to Connect

Remote Large

Display

Number of Ports

Used to

Interconnect

Switches

Number of Ports

Available to

Connect Liebert iCOM

Control Devices

Liebert vNSA8-Liebert

iCOM

Yes

8

1

-

7

Liebert vNSA16-

Liebert iCOM

16

1

2

13

Liebert vNSA8

No

8

-

-

8

Liebert vNSA16

16

-

2

14

P65

P64

(RJ-45 Jack)

P66

P63

P61

P67