Installing a Liebert iCOM Unit-to-Unit Network

44

5.3.1 Wiring a Liebert iCOM U2U Network

Small Displays

Two cooling units, each with a small display: To network two cooling units, each with a small

display, connect a crossover CAT5 cable between the P64 connectors on each cooling unit’s Liebert

iCOM input/output board. A network switch is not needed (see Figure 24).

Figure 24 Connecting two cooling units, each with a small display using a crossover Ethernet cable

Three or more units with small displays: To network three or more cooling units, each equipped

with a small display, connect a straight-through CAT5 Ethernet cable from the P64 connector on each

cooling unit’s Liebert iCOM input/output board to a common network switch (see Figure 26).

Large Displays

A network switch is required to enable Ethernet communication on one or more cooling units with

large displays. Each cooling unit with a large display requires two straight-through Ethernet cables

from a network switch. One cable connects to port P64 on the Liebert iCOM input/output board and

the other straight-through cable connects to the female-female coupler provided with the unit. Con-

nect the red crossover cable, which is provided with the cooling unit, between the coupler and the P64

port on the back of the large display (see Figure 28).

Wall-Mount Large Display

Only large displays can be used for remotely monitoring and controlling cooling units connected on

the same network. Each wall-mount large display requires 120V input power; Liebert provides an AC

adapter wall plug. A straight-through Ethernet cable must be connected between the network switch

and the P64 port on the back of the display. This will enable control and monitoring capabilities to

any cooling unit connected to the network. See 6.0 - Mounting a Large Display on a Wall for

mounting details and Figure 31 for wall-mount dimensions.

Combining Large and Small Displays on a U2U Network

Setting up a network of cooling units equipped with large and small displays requires a network

switch. The controls are to be connected to the switch as described above.