Table 27 diagnostics / service mode parameters, Table 27, Diagnostics / service mode parameters – Emerson Liebert iCOM User Manual

Page 67

Advertising
background image

Service Menu Parameters

61

Table 27

Diagnostics / service mode parameters

Function

Read/

Write

Range

Imperial (metric)

Large Display

Small Display

Page 1 of 7
Password

PASSWORD

W

-

HP 1 Alarm Code

HP1 CODE

W

0-999

HP 2 Alarm Code

HP2 CODE

W

0-999

HT 1 Alarm Counter

HT1 CNT

W

0-999

HT 2 Alarm Counter

HT2 CNT

W

0-999

LP 1 Alarm Code

LP 1 CODE

W

0-999

LP 2 Alarm Code

LP2 CODE

W

0-999

Actual LP1 Pressure

LP1 ACT

R

- 145.0 - 725.0 psi

(-10.0 to 50.0 bar)

Actual LP2 Pressure

LP2 ACT

R

- 145.0 - 725.0 psi

(-10.0 to 50.0 bar)

Actual HP1 Pressure

HP1 ACT

R

- 145.0 - 725.0 psi

(-10.0 to 50.0 bar)

Actual HP2 Pressure

HP2 ACT

R

- 145.0 - 725.0 psi

(-10.0 to 50.0 bar)

Page 2 of 7
Password

PASSWORD

W

-

Manual Mode

MANUAL

W

No, Yes

Motor(s)

MOTOR(S)

W

Off, On

Compressor 1

COMP1

W

Off, On

Compressor 1

C1 MODE

W

Run, Evacuate, Charge

Compressor 1 Capacity

C1 CAP

W

Off, On

Compressor 1 Cycle Ramp

C1 CYCLE

W

0-100%

Compressor 1 LLSV

LLSV 1

W

Off, On

Compressor 2

COMP2

W

Off, On

Compressor 2

C2 MODE

W

Run, Evacuate, Charge

Compressor 2 Capacity

C2 CAP

W

Off, On

Compressor 2 Cycle Ramp

C2 CYCLE

W

0-100%

Compressor 2 LLSV

LLSV 2

W

Off, On

Page 3 of 7
Password

PASSWORD

W

-

Electric Heat 1 (or HG/HW)

EL HEAT1

W

Off, On

Electric Heat 2 (or E.Heat 1)

EL HEAT2

W

Off, On

Electric Heat 3 (or E.Heat 2)

EL HEAT3

W

Off, On

SCR Heat

SCR HEAT

W

0-100%

Dehumidification Output

DEHUM

W

Off, On

Humidfier Fill

HUM FILL

W

Off, On

Humidifier

HUM

W

Off, On

Humidfier Drain

H DRAIN

W

Off, On

Humidifier Current

HUM.C.

R

0.00 - 99.99A

Page 4 of 7

SERVICE