0 firmware, 1 description of operation – Pressure Systems 9046 User Manual

Page 30

Advertising
background image

Pressure Systems, Inc. Model 9046 User’s Manual

Page 24

www.PressureSystems.com

4.0 Firmware

4.1 Description of Operation

Table 1 shows the different sensor types available along with the gain settings and engineering
units for each type. Setting channel sensor type automatically causes the gain for that channel
to be set according to Table1.

Sensor Type

Gain Setting
Va, Vb

Engineering
Units

Volts 1,

1

Volts

Thermocouple, Types:
B, E, J, K, N, R, S, T

90, 1

Degrees C (F)

Resistance
Range 220

Ω

Range 440

Ω

Range 990

Ω

Range 19.8 k

Ω


90, 90
45, 45
20, 20
1, 1

Ohms

Thermistor
2.25 k, 5 k, 10 k


1, 1

Degrees C (F)

Platinum RTD
(100

Ω at 0 °C

+ 0.385

Ω/°C)

90, 90

Degrees C (F)

MIL-T-7990B RTD

90, 90

Degrees C (F)

The two voltages for each channel are read during each pass through the data acquisition task.
Default number of averages is 64 and default thermal updates is 15 seconds. Va is the
transducer voltage. Vb is the voltage of the cold junction transducer. These voltages are used
to calculate engineering units for each channel as follows: