Description of the XCL8010AU Controller Module Excel

800

EN1B-0410GE51 R0908A

10

Corresponding Terminal Sockets

Table 6. I/O modules and corresponding terminal sockets

I/O module

socket

scope of delivery

XF821AU,
XFL821AU

XF822AU,
XFL822AU,
XFLR822AU,
XFR822AU

XS821-22

1 terminal socket,
1 bridge connector
1 swivel label holder

XF823AU,
XFL823AU

XS823

1 terminal socket,
1 bridge connector
1 swivel label holder

XF824AU,
XFL824AU,
XFLR824AU,
XFR824AU

XFR825AU

XS824-25

1 terminal socket,
1 bridge connector
1 swivel label holder
1 long cross connector

Interfaces and Bus Connections

The Excel 800 System can be connected to the following
devices and systems:

Panel Bus
• For communication with up to 16 Panel Bus I/O modules
• Polarity-insensitive

LonWorks Bus
• For communication with other L

ON

W

ORKS

Bus devices

within the building

• FTT10, link power compatible
• Polarity-insensitive

C-Bus
• For communication with other controllers

HMI
• For connecting an operator interface, e.g., XI582 or a

laptop, e.g., for CARE


Modem
• NO CONNECTION

Technical Data

System Data

Table 7. System data

Operating voltage

24 VAC/DC, 60 Hz

Power consumption

Max. 3.57 A
(1 XCL8010AU Controller
+ 16 I/O modules)

Operational Environment

Table 8. Operational environment

ambient operating
temperature

0 ─ 49 °C (32 ─ 122 °F)

ambient operating
humidity

5 ─ 93 % rel. humidity
(non-condensing)

ambient storage
temperature

–20 ─ +70 °C (–4 ─ +158 °F)

ambient storage
humidity

5 ─ 95 % rel. humidity
(non-condensing)

Smoke Control Configuration

XL800

2

3

4

5

6

7

9

10

11

12

8

UL-LISTED
FIRE ALARM

CONTROL UNIT

SMOKE CONTROL CONFIGURATION

FIREFIGHTERS’
SMOKE CONTROL

PANEL (FSCS)

14505068

AUDIBLE
ANNUNCIATOR

STATUS CONTROL

VERIFICATION

DAMPER

AIRFLOW SENSOR

1

AO

AO

AO

SUPPLY
FAN

EXHAUST

FAN

Fig. 8. Typical smoke control configuration

NOTES:

1

Locate and configure per NFPA 92A, Section 3-4.3.4.

UL-listed annunciator / FSCS panel switches have a
minimum rating of 24 V, 1/10 Amp, and lamps / LEDs
have a rating of 24 V, limited to 50 mA.

2

Locate so as to minimize control wiring and piping.

Avoid running wires or piping through areas that have
a high fire risk.

3

Locate per UL 555S.