Troubleshooting, Testing wiring connections, Troubleshooting on the xcl8010au controller – Honeywell XL 800 SERIES User Manual

Page 31: Power led (green)

Advertising
background image

Excel 800

Troubleshooting

31

EN1B-0410GE51

R0908A

Troubleshooting

Testing Wiring Connections

The push-in terminals feature small holes (1 mm in diameter)
which can be used to measure the signals.

Insert a probe (1) as shown on the right.

Fig. 49. Testing wiring connections

Troubleshooting on the XCL8010AU Controller

The following LEDs of the XCL8010AU Controller can be used for troubleshooting purposes:

Power LED (green)

Alarm LED (red)

L

ON

W

ORKS

service LED

C-Bus Tx and Rx LEDs

HMI Tx and Rx LEDs

Power LED (green)

Table 37. XCL8010AU power LED

case

power LED

meaning

remedy

1 ON

Normal operation

No action necessary

2 Flashing

One or more of the internal voltage supplies
are outside of the permissible ranges. The
controller stops operation.

Check power

Check wiring

If problem persists, replace hardware

3 Goes

out

briefly

• The operator has activated the reset button
• The controller is performing a warm start

No action necessary