C-bus tx and rx leds, Hmi tx and rx leds – Honeywell XL 800 SERIES User Manual

Page 33

Advertising
background image

Excel 800

Troubleshooting

33

EN1B-0410GE51

R0908A

Table 39. XCL8010AU L

ON

W

ORKS

service LED

case

When can it occur?

meaning

remedy

1

Anytime

Node is configured and running normally

No action necessary

2

Power up of controller

Bad node hardware

Replace hardware

3

Power up of controller

Bad node hardware

Replace hardware

4

Power up / reset

Node lacks application.
May be caused by neuron chip firmware when
a mismatch occurs on application checksum

Using EXCELON, set module to
“configured online”

If problem persists, the MIP software
on LW interface has been erased due
to wrong setting performed using
ECHELON tool:
Replace hardware

5

Anytime

Watchdog timer resets occurring.
Possible corrupt EEPROM and bootstrap
mode

Download firmware

6

Anytime

Node is unconfigured but has an application

Proceed with commissioning

C-Bus Tx and Rx LEDs

Table 40. XCL8010AU C-Bus Tx and Rx LEDs

case

C-Bus LEDs

meaning

remedy

If the C-bus is functioning properly, then the
XCL8010AU is functioning properly

No action necessary

1

Both LEDs are flashing

If the C-bus is not functioning properly, then
the termination can be wrong

Check C-bus termination switch S1
(location: see Fig. 4 on page 7)

2

Both LEDs are OFF

No C-bus communication

Check C-bus settings

3

Both LEDs are flashing
synchronously

No C-bus communication

Check C-bus wiring

HMI Tx and Rx LEDs

Table 41. XCL8010AU HMI Tx and Rx LEDs

case

HMI LEDs

meaning

remedy

1

Both LEDs are flashing

If the HMI Interface is functioning properly,
then the XCL8010AU is functioning properly

No action necessary

2

Both LEDs are OFF

No HMI Interface communication

Check HMI Interface connection and
proper earthing of connected
hardware