Mounting/dismounting modules, Setting the i/o bus switch, Bus topologies – Honeywell XL 800 SERIES User Manual

Page 14: C-bus topologies, Warning

Advertising
background image

Mounting/Dismounting Modules

Excel 800

EN1B-0410GE51 R0908A

14

LOCK

4

4

Fig. 14. HEX switch location


NOTE:

If the HEX switch setting is changed, the Panel
Bus I/O module will revert to its default
configuration. With L

ON

W

ORKS

Bus I/O modules,

the HEX switch is without function.

Setting the I/O Bus Switch

Set the I/O Bus switch S2 of the XCL8010AU

Controller

Module depending on the modules connected to terminals
71 ─ 78 and the desired communication as follows:

Table 10. I/O Bus switch settings

communication

S2 setting

terminals

L

ON

W

ORKS

Bus

only

LON 71

─ 74 L

ON

W

ORKS

Bus

75 ─ 78

L

ON

W

ORKS

Bus

11 ─ 14

L

ON

W

ORKS

Bus

Panel Bus and
L

ON

W

ORKS

Bus

Panel 71

─ 74 Panel Bus

75 ─ 78 Panel Bus
11 ─ 14 L

ON

W

ORKS

Bus

Fig. 15. S2 I/O Bus switch

L

ON

W

ORKS

Bus Topologies

The L

ON

W

ORKS

Bus is a 78-kilobit serial link that uses

transformer isolation so that the bus wiring does not have a
polarity. I.e. it is not important which of the two L

ON

W

ORKS

Bus terminals are connected to each wire of the twisted pair.
The L

ON

W

ORKS

Bus does not need to be shielded on the

controller module side.
The L

ON

W

ORKS

Bus can be wired in daisy chain, star, loop or

any combination thereof as long as the maximum wire length
requirements are met.

Configuration
The recommended configuration is a daisy chain with two bus
terminations. This layout allows for max. L

ON

W

ORKS

Bus

lengths, and its simple structure presents the least number of
possible problems, particularly when adding on to an existing
bus.

C-Bus Topologies

Via the C-Bus up to 30 C-Bus devices (e.g., controllers, etc.)
can communicate with one another and a PC central. The C-
Bus must be connected via the individual controllers (open
ring).

NOTE:

Star connection is not allowed because
uncontrollable line reflections may occur.

Mounting/Dismounting Modules

WARNING

Risk of electric shock or equipment damage!

Do not touch any live parts in the cabinet.

Disconnect the power supply before you start to install the
Excel 800 System.
More than one disconnect switch may be required to de-
energize the system.

Do not reconnect the power supply until you have
completed the installation.


NOTE:

The terminal socket of each I/O module can be
mounted and wired before inserting and locking
the corresponding electronic module.

Advertising