XCL8010AU, I/O Modules on Single Rail

Connect XCL8010AU Controller Module and I/O modules
using the bridge connectors.

This provides power supply and communication connection.
No further wiring is necessary.

Multiple Rails in Single Cabinet

The multiple rails of a controller system are connected in
series.

Connect the rail ends as follows:
Power supply

via power supply terminals 73, 74 or 77, 78

Communication

via communication terminals 71, 72 or 75, 76

I/O MODULE

XCL8010AU

1 2

I/O MODULE

71

72

73

74

I/O MODULE

71

72

73

74

I/O MODULE

71

72

73

74

I/O MODULE

75

76

77

78

I/O MODULE

75

76

77

78

I/O MODULE

71

72

73

74

Fig. 10. Wiring the power supply and the communication

lines to the I/O modules

LonWorks Bus I/O Modules in Separate Rooms

In this scenario, only communication lines must be connected
between the rooms.

Connect the last module of room 1 to the first module of
room 2:
– via communication terminals 71, 72 or 75, 76

XCL8010AU

1 2

71

72

73

74

ROOM 2

ROOM 1

LonWorks

I/O MODULE

LonWorks

I/O MODULE

73

74

LonWorks

I/O MODULE

LonWorks

I/O MODULE

LonWorks

I/O MODULE

78

75

76

77

78

75

76

77

Fig. 11. Wiring the L

ON

W

ORKS

Bus I/O modules in

separate rooms


Maximum Cable Length
Max. cable length: 1200 meters (4000 ft), supervised.

How to Connect Panel Bus and L

ON

W

ORKS

Bus Mixed Controller Systems

Connecting I/O Modules

For connecting the I/O modules with each other, proceed as
described for single-bus controller systems.

Connecting I/O Modules to the XCL8010AU

Panel Bus I/O Modules

Connect communication terminals 71 ─ 74 or 75 ─ 78 of
Panel Bus I/O modules to communication terminals 71 ─
74 or 75 ─ 78 of the XCL8010AU Controller Module using
either
– Bridge connectors

for flush mounting on a single DIN rail or

– Cables

for separate mounting, e.g., on multiple rails, separate
cabinets, etc.


L

ON

W

ORKS

Bus I/O Modules

Connect communication terminals 71 ─ 74 or 75 ─ 78 of
L

ON

W

ORKS

Bus I/O modules to L

ON

W

ORKS

terminals 11 ─

14 of the XCL8010AU using cables.