C-bus tx led and rx led, Reset button, Hmi interface – Honeywell XL 800 SERIES User Manual

Page 19: Notice

Advertising
background image

Excel 800

Mounting/Dismounting Modules

19

EN1B-0410GE51

R0908A

C-Bus Tx LED and Rx LED

The XCL8010AU

Controller Module is equipped with a Tx

LED (status: yellow/OFF) and an Rx LED (status:
yellow/OFF).

1

C-Bus

2

Fig. 29. C-Bus Tx LED (1) and Rx LED (2)


C-Bus LEDs

Table 14. Controller C-Bus LEDs

Tx (1)
flickering

The controller is sending data onto the
C-Bus

Rx (2)
flickering

The controller is receiving data from the
C-Bus

Reset Button

The XCL8010AU

Controller Module is equipped with a reset

button.

1

RESET

Fig. 30. Reset button (1)


Pushing the reset button (1), e.g. using a paperclip, will cause
the XCL8010AU

Controller Module to reset.


NOTE:

In the event of a reset, all non-volatile memory
contents are permanently deleted, though the
clock will not be set to zero. In order to avoid
problems, we therefore recommend that you
always save your application changes (e.g., time
program changes) to FLASH memory.

HMI Interface

The XCL8010AU

Controller Module is equipped with an HMI

Interface for the connection of HMIs, e.g., XI582 Operator
Interface or a laptop (with XL-Online/CARE).

Fig. 31. HMI interface, Tx LED (1) and Rx LED (2)


HMI interface LEDs on RJ45 socket

Table 15. HMI interface LEDs

Tx (1)
flickering

The controller is transmitting data to the HMI

Rx (2)
flickering

The controller is receiving data from the HMI


HMI interface Signals on RJ45 socket

Table 16. Signals of the HMI interface

pin

signal type

1 -

2 Receive

3 Transmit

4 -

5 Signal

ground

6 -

7 5

V

8 -

NOTICE

Equipment damage!

If earth grounding is required, make sure that only terminal
2 is connected to earth ground. Terminal 1 must not be
connected to earth ground. See also Appendix 1.