I/o modules troubleshooting, Power led of i/o modules – Honeywell XL 800 SERIES User Manual

Page 34

Advertising
background image

Excel 800

EN1B-0410GE51 R0908A

34

I/O Modules Troubleshooting

Check if the power supply voltage level is OK and that there is no high voltage (> 24 VAC or > 40 VDC) connected to the
inputs/outputs of the XF821AU, XFL821AU, XF822AU, XFL822AU, XFR822AU, XFLR822AU, XF823AU, and XFL823AU I/O
modules.

Replace the problem I/O module with another module of the same kind.
– If the problem persists, this is an indication that the problem is caused by the application or incorrect wiring.
– If the problem is solved, this is an indication that the I/O module was defective.


For troubleshooting purposes on all I/O modules the following features can be used:
• Power

LED

• Service

LED

• Service

button

In addition, a module-specific troubleshooting may be necessary.

Power LED of I/O Modules

Table 42. Power LED of I/O modules

case

power LED

meaning

remedy

1 ON

I/O module is powered

No action necessary

2 OFF

No power

Check power supply

3 Flashing

continuously

If the I/O module’s service LED is likewise
flashing, the I/O module is in the boot mode

Wait until rebooting (firmware
download) has been completed