Connecting via c-bus, Connecting hmis or laptops, Dismounting electronic modules – Honeywell XL 800 SERIES User Manual

Page 17: Connecting to the controller, Setting the c-bus termination switch, Shielding, Connecting the xi582 operator interface

Advertising
background image

Excel 800

Mounting/Dismounting Modules

17

EN1B-0410GE51

R0908A

Fig. 23. Locking the electronic module


NOTE:

The red locking mechanism will not close if the
electronic module is not properly mounted.

Dismounting Electronic Modules

NOTE:

Electronic modules can be removed from the
socket or inserted into the sockets without
switching off the power supply. The behavior of
connected field devices must be taken into
consideration.

Open the red locking mechanism by sliding it to the left
and then gently pull the electronic module out of the
terminal socket.

Fig. 24. Dismounting the electronic module

Connecting via C-Bus

Via C-Bus, an XCL8010AU Controller Module can be
connected to other controller systems to form a network.

Connecting to the Controller

Connect the C-Bus to the XCL8010AU Controller Module
as follows:
– Input to C-Bus terminals 8 and 9
– Output to C-Bus terminals 5 and 6
– Do not connect the C-Bus to the cabinet earth or any

other earth ground points

Setting the C-Bus Termination Switch

Set the C-Bus termination switch S1 appropriately.

Fig. 25. C-Bus termination switch S1

Table 11. XCL8010AU

C-Bus termination switch settings

switch setting

S1

baud rate

9.6k all

Up to 9600 baud (default setting)

76k mid

Up to 76800 baud without bus termination

76k end

Up to 76800 baud with bus termination

Shielding

In principle, data transmitting cables should be shielded in
case of RFI.

On the controller side, connect the shield to terminals 7
and 10.

On the side of the device, connect the shield to the
respective terminals.
Do not connect it to the cabinet ground or any other
ground points.

Connecting HMIs or Laptops

Laptops or HMIs, e.g., XI582, can either be connected via the
HMI interface of the XCL8010AU Controller Module or via the
L

ON

W

ORKS

interface.

Connecting the XI582 Operator Interface

Connect the XI582AH Operator Interface to the HMI
interface or L

ON

W

ORKS

interface of the XCL8010AU

Controller Module by means of
– the XW882 cable or
– the XW582 cable connected with an XW586 cable.